1.EST3 Description
The EST3 External Communications Protocol (ECP) driver allows the FieldServer to transfer data to and from EST devices over
The FieldServer makes use of the following ECP Services:
Read Operations:
•Report Service
•Delta Service Write Operations:
•Command Service
All read points are continually updated using the Report Service; response times are enhanced using Delta Service broadcasts by the EST3 panel.
The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer.
2.Driver Scope of Supply
2.1.Supplied By FieldServer Technologies for this Driver
FIELDSERVER |
| DESCRIPTION |
|
TECHNOLOGIES PART # |
|
| |
|
|
| |
7’ Patch Cable | |||
RJ45 to DB9M Connector adapter | |||
DB9F to terminal Adapter | |||
EST3 ECP Driver Manual |
2.2.Provided By the Supplier of 3rd Party Equipment
2.2.1.Hardware
PART # | DESCRIPTION | VERSION |
| EST3 Gateway |
|
|
|
|
2.2.2.Required 3rd Party Configuration
The EST3 panel has to be set into the “Gateway Mode” using the EST3 Configuration tool (3- SDU)
Possible Protocols |
|
ECP Type II | Supported |
ECP Type II with Text | Not Supported |
ECP Type III | Supported |
ECP Type III with Text | Not Supported |