| Page 19 of 21 |
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Type | Encode | Alarm | Trouble | Supervisory | Monitor | Others |
|
|
| Value |
|
|
|
|
|
|
| AccessReaderFault | 148 |
|
|
|
| Y |
|
|
|
|
|
|
|
|
|
|
| AccessInternalFault | 149 |
|
|
|
| Y |
|
|
|
|
|
|
|
|
|
|
| AccessCommunicationFault | 150 |
|
|
|
| Y |
|
|
|
|
|
|
|
|
|
|
| CmdList | 151 |
|
|
|
| Y |
|
Appendix C.2. Output data format
Each output device is associated with a
FieldServer Data Array Object
Attribute | Command |
These values are provided by the EST panel and are described in the EST3 ECP protocol specification as follows. These values will be put in the Command field.
Command | Encode Value |
Activate / Away | 01h |
Enable | 02h |
Restore / Disarm | 11h |
Disable | 12h |
The attribute byte must be set for writes to Relay and LED outputs. For Relays, the attribute values are:
Attribute (Relay) | Encode Value |
Enable | 2h |
Activate | 101h |
Restore | 11h |
Disable | 12h |
For LED’s, the attribute values are: |
|
|
|
Attribute (LED) | Encode Value |
On | 101h |
Slow Flash | 201h |
Fast Flash | 301h |
Disable | 12h |
Enable | 2h |
Off | 1h |
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com