4.4.Client Side Map Descriptors

4.4.1.FieldServer Related Map Descriptor Parameters

Column Title

Function

Legal Values

Map_Descriptor_Name

Name of this Map Descriptor

Up to 32 alphanumeric

characters

 

 

Data_Array_Name

Name of Data Array where data

One of the Data Array names

is to be stored in the FieldServer

from “Data Array” section above

 

Data_Array_Offset

Starting location in Data Array

0 to maximum specified in “Data

Array” section above

 

 

Function

Function of Client Map Descriptor

RDBC, WRBC3, WRBX

4.4.2.Driver Related Map Descriptor Parameters

Column Title

Function

 

Legal Values

 

 

One of the node names

Node_Name

Name of Node to fetch data from

specified in “Client Node

 

 

Descriptor” above

EST_Panel

Panel

0

- 63

EST_Card

Card

0

- 255

Address

Starting address of read block

0

- 1023

Length

Length of Map Descriptor

For Reads: 1 to 34 For Writes:

1

 

 

 

 

 

 

Relay, Led, ServGroup,

 

 

GuardPtrl, ChkInGrp,

 

 

AltMessage, Reset, PanelSil,

 

 

AlarmSil, Drill, GAInhibit,

EST_Object_Type

Object type parameter

Reboot, Evacuate, AltSensitiv,

Partition, CmdList, Input, Zone,

 

 

 

 

Card, AndGroup, Matrix,

 

 

TimeCtrl, InstructionText,

 

 

AmpPower, AudMsg, CmdList,

 

 

MCmsg, SetDate, SetTime

EST_Index

Index parameter

0

- 65535

EST_Route

Route parameter

0

- 255

EST_Priority

Pri parameter

0

- 4 (see note below)

EST_Chan

Chan parameter

0

- 255

EST_Msg_Index

MsgIndex parameter

0

- 65535

EST_Account

Account parameter

0

- 255

EST_ConfCL

ConfCL parameter

0

- 65535

EST_Panel_Mask_1

PanelMask(1) parameter (LSB)

0

- 255

EST_Panel_Mask_2

PanelMask(2) parameter

0

- 255

EST_Panel_Mask_3

PanelMask(3) parameter

0

- 255

EST_Panel_Mask_4

PanelMask(4) parameter

0

- 255

EST_Panel_Mask_5

PanelMask(5) parameter

0

- 255

EST_Panel_Mask_6

PanelMask(6) parameter

0

- 255

EST_Panel_Mask_7

PanelMask(7) parameter

0

- 255

EST_Panel_Mask_8

PanelMask(8) parameter (MSB)

0

- 255

Data_Array_Low_Scale*

Scaling zero in Data Array

-32767 to 32767, 0

 

 

 

Data_Array_High_Scale*

Scaling max in Data Array

-32767 to 32767, 100

 

 

 

Node_Low_Scale*

Scaling zero in Connected Node

-32767 to 32767, 0

Node_High_Scale*

Scaling max in Connected Node

-32767 to 32767, 100

3WRBC is not recommended, as startup values may be invalid

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Image 7
Contents Applicability & Effectivity Driver Manual FS-8700-39 EST3 ECPTable of Contents ECP Type III with Text Required 3rd Party ConfigurationEST3 Description Provided By the Supplier of 3rd Party Equipment Hardware FieldServerP1 Hardware ConnectionsData Arrays Configuring the FieldServer as a EST3 ClientUINT16 EST1 EST3 Client Side Connection DescriptorsClient Side Node Descriptors EST3RDBC, Wrbc 3, Wrbx Driver Related Map Descriptor ParametersPage Map Descriptor Example Appendix A.3. Priority Appendix A.2. Setting up Multiple ParametersAppendix A.4. Report and Delta Service Appendix A. Driver Notes Appendix A.1. PanelMasksDatrouble Appendix A.4.1. Example Configuration using Delta Mode onlyDaalarm DATEST1Appendix A.5.2. ESTTypesDA Appendix A.5.3. ESTTypesUpdateAppendix A.5. Optional Data Arrays Appendix A.5.1. Relay Confirmation StateAppendix A.5.5. ESTReportType Partition Appendix A.6. Object Types and Required ParametersAppendix A.7. Set Date and Time To Panel FS-8700-39 EST3 Driver Manual Appendix C. EST3 Data Format Appendix C.1. Input data format Page Appendix C.2. Output data format Appendix D. EST3 ECP Connection Statistics Appendix E. Driver Error Messages