Appendix E. Driver Error Messages
Error Message | Description and Action Required | |
| This message will be displayed once if any Map Descriptor in a configuration | |
EST3:#01 FYI. For an | file has an odd length. Old EST3 Panels (before 2002) simply do not | |
communicate if length is odd. | ||
Old EST3 Panel, Read | ||
This message can be ignored if it is new EST3 panel. But if it is old or | ||
MD length must be even. | ||
unknown, try making Map Descriptor having even length before contacting | ||
| technical support. | |
EST3:#02 Err. Read MD | Numbers of addresses to be read per request are limited. | |
length must > 0 and <= | ||
Edit configuration file to set Map Descriptor length within specified range.6 | ||
%d |
| |
EST3:#03 Err. Write MD | One Map Descriptor can write only 1 value. Change length to 16. | |
must have length = 1 |
| |
EST3: #04 Unknown | This message is printed if the FieldServer receives sequences that are not | |
Escape Sequence 1B | specified. Specified sequences are 1B 82, 1B 8D and 1B 9B. This message | |
%02X considered as | is for information only and can be ignored unless the data stored by the | |
%02X | FieldServer is invalid in which case, call Tech support. |
6Download the configuration file, make the necessary changes, upload to the FieldServer and cycle power to the FieldServer for the changes to take effect.