Appendix A.5. Optional Data Arrays
When optional parameters (EST_Alarm_DA, EST_Trouble_DA, EST_Supervisory_DA, or EST_Monitor_DA) are used, the driver automatically separates the Alarm Trouble, Supervisory, and Monitor bit from the incoming EST message and places the bit(s) in these Data Arrays at the same offset as the incoming message. Other types can be stored in EST_Others_DA Data Array. Only one Data type will be reported as active at a particular time; i.e. if Alarm is reported Driver will set Alarm bit and reset corresponding bits from Trouble, Supervisory and Monitor Data Arrays. The Driver does not correlate Other types with Alarm, Trouble, Supervisory or Monitor types. For different point types the active bit has a different meaning. If the user is interested in the meaning, the EST_Supervisory_DA Data Array should be configured. If the user is interested in the raw value of the Active bit, the data array EST_Active_DA should be configured.
Appendix A.5.1. Relay Confirmation State
The driver can store the relay confirmation state of a point in a Data Array under the parameter
EST_Relay_Conf_DA parameter. |
|
0 - Relay state is not confirmed; | 1 – Relay state confirmed. |
Appendix A.5.2. EST_Types_DA
If it is necessary to override the default Types and Category list (Appendix C.1) the EST_Types_DA parameter should be used.
Example:
To put HEAT type into the “Monitor” category where all other defaults remain the same, preload the data array as follows:
Preloads |
|
|
|
Data_Array_Name | ,Preload_Data_Index | ,Preload_Data_Value | ,Length |
DA_Types | ,2 | ,4 | ,1 |
Preload_Data_Index is the type of device and Preload_Data_Value holds the category for the specified device type. The legal values for Preload_Data_Value are listed below
Alarm | 1 |
Supervisory | 2 |
Trouble | 3 |
Monitor | 4 |
Others | 5 |
Appendix A.5.3. EST_Types_Update
If this parameter is not defined or is “yes”, the driver will update its internal driver list according to the parameters preloaded under EST_Types_DA. If the parameter is set to “New List”, the driver will use ONLY the parameters defined under EST_Types_DA and will not reference or update the default list at all. The driver will therefore not store any data for types that do not have preloaded categories.
Appendix A.5.4. DA_Bit_Name
The ”Acknowledge5” state of a point is stored under this Data Array if configured.
0 – Acknowledged or Acknowledge not required.
1 – Point is not Acknowledged yet. To Acknowledge the point change the value to “0”.
5The EST3 panel is only able to send/accept Acknowledgement when the panel is in Proprietary Mode. Contact EST (Edwards Systems Technology) for information on configuring the panel.