FieldServer FS-8700-19 instruction manual TYPE8

Page 37

FS-8700-19_Metasys_N2 Driver Manual

 

Page 37 of 51

 

 

 

 

 

 

 

 

 

 

 

 

 

PAGE 0

 

 

 

Item

Item

Signal Condition

Read/Write

Johnson

Description

 

 

DEC

HEX

Tag

 

 

 

 

 

 

 

180

B4

Byte

Write

TYPE8

Controller type

 

 

181

B5

FP

Write

LS8

Local setpoint

 

 

182

B6

FP

Write

PB8

Proportional band

 

 

183

B7

FP

Write

TI8

Reset action

 

 

184

B8

FP

Write

TD8

Rate action

 

 

185

B9

FP

Write

HL8

Upper limit of the control output

 

 

186

BA

FP

Write

LL8

Lower limit of the control output

 

 

187

BB

FP

Write

BS8

Change of setpoint during STAND-BY

 

 

188

BC

FP

Write

BO8

Change of setpoint during OFF

 

 

189

BD

FP

Write

AD8

Deviation alarm

 

 

190

BE

Byte

Write

IR1

Range analog input 1

 

 

191

BF

FP

Write

HA1

High alarm input 1

 

 

192

C0

FP

Write

LA1

Low alarm input 1

 

 

193

C1

FP

Write

FI1

Filter time input 1

 

 

194

C2

Byte

Write

IR2

Range analog input 2

 

 

195

C3

FP

Write

HA2

High alarm input 2

 

 

196

C4

FP

Write

LA2

Low alarm input 2

 

 

197

C5

FP

Write

FI2

Filter time input 2

 

 

198

C6

Byte

Write

IR3

Range analog input 3

 

 

199

C7

FP

Write

HA3

High alarm input 3

 

 

200

C8

FP

Write

LA3

Low alarm input 3

 

 

201

C9

FP

Write

FI3

Filter time input 3

 

 

202

CA

Byte

Write

IR4

Range analog input 4

 

 

203

CB

FP

Write

HA4

High alarm input 4

 

 

204

CC

FP

Write

LA4

Low alarm input 4

 

 

205

CD

FP

Write

FI4

Filter time input 4

 

 

206

CE

Byte

Write

IR5

Range analog input 5

 

 

207

CF

FP

Write

HA5

High alarm input 5

 

 

208

D0

FP

Write

LA5

Low alarm input 5

 

 

209

D1

FP

Write

FI5

Filter time input 5

 

 

210

D2

Byte

Write

IR6

Range analog input 6

 

 

211

D3

FP

Write

HA6

High alarm input 6

 

 

212

D4

FP

Write

LA6

Low alarm input 6

 

 

213

D5

FP

Write

FI6

Filter time input 6

 

 

214

D6

Byte

Write

IR7

Range analog input 7

 

 

215

D7

FP

Write

HA7

High alarm input 7

 

 

216

D8

FP

Write

LA7

Low alarm input 7

 

 

217

D9

FP

Write

FI7

Filter time input 7

 

 

218

DA

Byte

Write

IR8

Range analog input 8

 

 

219

DB

FP

Write

HA8

High alarm input 8

 

 

220

DC

FP

Write

LA8

Low alarm input 8

 

 

221

DD

FP

Write

FI8

Filter time input 8

 

 

222

DE

FP

Write

OH1

Output 1 high range

 

 

223

DF

FP

Write

OL1

Output1 low range

 

 

224

E0

Byte

Write

OMS1

Source of analog output module 1

 

 

225

E1

FP

Write

OH2

Output 2 high range

 

 

226

E2

FP

Write

OL2

Output 2 low range

 

 

227

E3

Byte

Write

OMS2

Source of analog output module 2

 

 

228

E4

FP

Write

OH3

Output OUTA1 high range

 

 

229

E5

FP

Write

OL3

Output OUTA1 low range

 

 

230

E6

Byte

Write

OMS3

Source of logic output module OUTA

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 37
Contents FS-8700-19 Metasys N2 Table of Contents Metasys N2 Description Provided by the Supplier of 3rd Party Equipment Hardware Required 3rd Party ConfigurationRequired 3rd Party Software Hardware Connection Tips / Hints Hardware ConnectionsData Arrays/Descriptors Configuring the FieldServer as a Metasys N2 ClientClient Side Connection Descriptions Client Side Node Descriptors AI, AO, DI, do Object Configuration VMA Map Descriptor Parameters ADF ADI Timing Parameters 2.3. DX9100 Map Descriptor ParametersMap Descriptor Example 2 VMA Map Descriptor Example 1 N2OpenDAAO3 Wrbx Map Descriptor Example 3 DX9100Server Side Connection Descriptors Configuring the FieldServer as a Metasys N2 ServerServer Side Node Descriptors Driver Specific Map Descriptor Parameters Map Descriptor Example FS-8700-19MetasysN2 Driver Manual Appendix A.2. Managing Analog Inputs and Outputs for DX9100 Appendix B.3. Tip on Overrides Appendix B.2. Offline BehaviorFS-8700-19MetasysN2 Driver Manual FS-8700-19MetasysN2 Driver Manual Appendix C.2. Hardware connections Appendix C.3. Configuration SettingsFS-8700-19MetasysN2 Driver ManualPage 26 SUP UnitMNT DiagPmopt PmtypPMF1 PMF2PMK33 PMK32PMK34 PMOU1DO@ DOTFB@ DOF@XTLOA6 XTHIA6XTHIA7 XTLOA7FS-8700-19MetasysN2 Driver Manual DEC HEX Appendix D.2. Metasys DC9100 Memory MapTYPE1 TYPE3 TYPE6 TYPE8 LR1 HR1HR2 LR2OSZT@ OsoptOSOT@ OSSP@Appendix D.3. Metasys TC9100 Memory Map ROS DO6 Triac DO7 DO1 DO2Mods ModtRAS LSCIAS AFMPM5K2 PM5TYPPM5K3 PM5K4OCN4 OCO3OCO4 OCN5TCS3 TCS2TCS1 HDW1FTC1 LRI1OFS1 IOP1FSP FT@Fdif LOODST2 DST1DST3 DST4DST6 DST5DST7 Error Message Description and Action Appendix E. Error MessagesThis page Intentionally Left Blank