FieldServer FS-8700-19 Osopt, Oszt@, Osot@, Ossp@, Osob@, Osdi@, Osda@, Osts@, Osnx@, Ostim@

Page 39

FS-8700-19_Metasys_N2 Driver Manual

 

Page 39 of 51

 

 

 

 

 

 

 

 

 

Optimal start / stop module

 

Relative Item

Signal Condition

Read/Write

Johnson Tag

Description

 

0

Byte

Write

OSOPT

Module options

 

1

Word

Write

OSZT@

Zone temperature connection

 

2

Word

Write

OSOT@

Outdoor temperature connection

 

3

Word

Write

OSSP@

Zone temperature setpoint connection

 

4

Word

Write

OSOB@

Off setpoint bias connection

 

5

Word

Write

OSDI@

Disable module connection

 

6

Word

Write

OSDA@

Disable adaptive action connection

 

7

Word

Write

OSTS@

Connection at time schedule output

 

8

Word

Write

OSNX@

Connection at next output

 

9

Word

Write

OSTIM@

Connection at time to next output

 

10

FP

Write

OSPURGE

Minimum cool / heat time (min)

 

11

FP

Write

OSMAXST

Maximum start up time (min)

 

12

FP

Write

OSMAXSO

Maximum shut down time (min)

 

13

FP

Write

OSBHK

Start mode building heating factor

 

14

FP

Write

OSBCK

Start mode building cooling factor

 

15

FP

Write

OSSBHK

Stop mode building heating factor

 

16

FP

Write

OSSBCK

Stop mode building cooling factor

 

17

FP

Write

OSFW

Percentage adaptive control (filter weight)

 

18

FP

Write

OSHTD

Outdoor heating design temperature

 

19

FP

Write

OSCTD

Outdoor cooling design temperature

 

20

FP

Write

OSCRNG

Control range

 

21

FP

Write

OSSP

Zone temperature on setpoint

 

22

FP

Write

OSOB

Zone temperature off setpoint

 

23

FP

Write

OSTIM

Remaining time to next event

 

24

Byte

Write

OSSTA

Operating status

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 39
Contents FS-8700-19 Metasys N2 Table of Contents Metasys N2 Description Required 3rd Party Configuration Provided by the Supplier of 3rd Party Equipment HardwareRequired 3rd Party Software Hardware Connection Tips / Hints Hardware ConnectionsData Arrays/Descriptors Configuring the FieldServer as a Metasys N2 ClientClient Side Connection Descriptions Client Side Node Descriptors AI, AO, DI, do Object Configuration VMA Map Descriptor Parameters ADF ADI Timing Parameters 2.3. DX9100 Map Descriptor ParametersMap Descriptor Example 2 VMA Map Descriptor Example 1 N2OpenDAAO3 Wrbx Map Descriptor Example 3 DX9100Server Side Connection Descriptors Configuring the FieldServer as a Metasys N2 ServerServer Side Node Descriptors Driver Specific Map Descriptor Parameters Map Descriptor Example FS-8700-19MetasysN2 Driver Manual Appendix A.2. Managing Analog Inputs and Outputs for DX9100 Appendix B.3. Tip on Overrides Appendix B.2. Offline BehaviorFS-8700-19MetasysN2 Driver Manual FS-8700-19MetasysN2 Driver Manual Appendix C.2. Hardware connections Appendix C.3. Configuration SettingsFS-8700-19MetasysN2 Driver ManualPage 26 Diag UnitSUP MNTPMF2 PmtypPmopt PMF1PMOU1 PMK32PMK33 PMK34DOF@ DOTDO@ FB@XTLOA7 XTHIA6XTLOA6 XTHIA7FS-8700-19MetasysN2 Driver Manual DEC HEX Appendix D.2. Metasys DC9100 Memory MapTYPE1 TYPE3 TYPE6 TYPE8 LR2 HR1LR1 HR2OSSP@ OsoptOSZT@ OSOT@Appendix D.3. Metasys TC9100 Memory Map Modt DO6 Triac DO7 DO1 DO2ROS ModsAFM LSCRAS IASPM5K4 PM5TYPPM5K2 PM5K3OCN5 OCO3OCN4 OCO4HDW1 TCS2TCS3 TCS1IOP1 LRI1FTC1 OFS1LOO FT@FSP FdifDST4 DST1DST2 DST3DST5 DST6DST7 Error Message Description and Action Appendix E. Error MessagesThis page Intentionally Left Blank