Page 7 of 51 |
4.2.Client Side Connection Descriptions
| Section Title |
|
|
| Connections |
|
|
| Column Title | Function | Legal Values |
| Port | Specify which port the device is | |
|
| connected to the FieldServer |
|
| Protocol | Specify protocol used | Metasys_N2 |
| Baud* | Specify baud rate | 9600 |
| Parity* | Specify parity | None |
| Data_Bits* | Specify data bits | 8 |
| Stop_Bits* | Specify stop bits | 1 |
|
|
| |
| Handshaking* | Specify hardware handshaking | None |
| Poll _Delay* | Time between internal polls | 0 |
| Line_Drive_On* | Duration of RTS assert before | 0.001s |
| start of transmission | ||
|
|
| |
| Line_Drive_Off* | Duration of RTS assert after | 0.000s |
| end of transmission | ||
|
| ||
|
|
| |
| Example |
|
|
//Client Side Connections
Connections
Port, Protocol
R1, Metasys_N2
1Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.