FieldServer FS-8700-19 instruction manual TCS2, TCS3, TCS1, HDW1, HRI1

Page 45

FS-8700-19_Metasys_N2 Driver Manual

 

 

 

 

Page 45 of 51

 

 

 

 

 

 

 

 

 

 

 

 

Input Output Config Parameters

 

 

 

Relative Item

Signal Condition

Read/Write

Johnson Tag

Description

 

 

 

 

W(14)

Read

 

Reset Cycle indication

 

 

 

W(15)

Read

 

00 = Power Up Reset

 

 

 



 

 

01

= External

Reset

 

 

 



 

 

10

= Oscillator Failure

 

 

 

W(16)

Read

 

11 = Watchdog Reset

 

 

133

Word

R/W

TCS2

TC9100 Controller Options

 

 

 

W(1)

 

 

00 Select Analog Input 1 ADC

 

 

 



 

 

to

 

 

 

 

 

 

W(2)

 

 

11 Select Analog Input 4 ADC

 

 

 

W(3)

 

 

TM9100 does not overrd the proc Variable

 

 

 

W(4)

 

 

Half

Alternate

Mode Timing

 

 

 

W(5)

 

 

0

=

Celsius

1 = Fahrenheit

 

 

 

W(6)

 

 

0 = 50 Hz 1 = 60 Hz Power Line

 

 

 

W(7)

 

 

Enable Facilitator Mode

 

 

 

W(8)

 

 

TRIAC7 is ON if mode is Comfort

 

 

 

W(9)

 

 

Digital Input #1 Mode

 

 

 



 

 

000

= Not used

 

 

 



 

 

001

= Window Open

 

 

 



 

 

010

= Occupancy Sensor

 

 

 



 

 

011

= Air Quality Sensor

 

 

 



 

 

100

= Reverse Action

 

 

 

W(11)

 

 

101

= Intrusion Alarm

 

 

 

W(12)

 

 

Negate Digital

Input #1

 

 

 

W(13)

 

 

Digital Input #2 Mode

 

 

 



 

 

000

= Not used

 

 

 



 

 

001

= Window Open

 

 

 



 

 

010

= Occupancy Sensor

 

 

 



 

 

011

= Air Quality Sensor

 

 

 



 

 

100

= Reverse Action

 

 

 

W(15)

 

 

101

= Intrusion Alarm

 

 

 

W(16)

 

 

Negate Digital

Input #2

 

 

134

Word

R/W

TCS3

Enable Jumper Options

 

 

 

W(1)

 

 

Enable Integral Zeroing Loop #1

 

 

 

W(2)

 

 

Enable Integral Zeroing Loop #2

 

 

 

W(3)

 

 

Enable Integral Zeroing Loop #3

 

 

 

W(4)

 

 

Enable Integral Zeroing Loop #4

 

 

 

W(5)

 

 

Enable Integral Zeroing Loop #5

 

 

 

W(6)

 

 

Enable Integral Zeroing Loop #6

 

 

 

W(7)

 

 

Not used

 

 

 

 

W(8)

 

 

Not used

 

 

 

 

W(9)

 

 

Enable Gain Doubling Loop #1

 

 

 

W(10)

 

 

Enable Gain Doubling Loop #2

 

 

 

W(11)

 

 

Enable Gain Doubling Loop #3

 

 

 

W(12)

 

 

Enable Gain Doubling Loop #4

 

 

 

W(13)

 

 

Enable Gain Doubling Loop #5

 

 

 

W(14)

 

 

Enable Gain Doubling Loop #6

 

 

135

Byte

Write

TCS1

Controller Options

 

 

 

B(1)

 

 

Not

used

 

 

 

 

B(2)

 

 

Not

used

 

 

 

 

B(3)

 

 

Not

used

 

 

 

 

B(4)

 

 

Not

used

 

 

 

 

B(5)

 

 

Not

used

 

 

 

 

B(6)

 

 

Not

used

 

 

 

 

B(7)

 

 

Not

used

 

 

 

 

B(8)

 

 

Default Action

1=Reverse

 

 

136

Word

R/W

HDW1

Hardware Configuration

 

 

137

FP

R/W

HRI1

High Range AI1

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 45
Contents FS-8700-19 Metasys N2 Table of Contents Metasys N2 Description Required 3rd Party Configuration Provided by the Supplier of 3rd Party Equipment HardwareRequired 3rd Party Software Hardware Connection Tips / Hints Hardware ConnectionsData Arrays/Descriptors Configuring the FieldServer as a Metasys N2 ClientClient Side Connection Descriptions Client Side Node Descriptors AI, AO, DI, do Object Configuration VMA Map Descriptor Parameters ADF ADI Timing Parameters 2.3. DX9100 Map Descriptor ParametersMap Descriptor Example 2 VMA Map Descriptor Example 1 N2OpenDAAO3 Wrbx Map Descriptor Example 3 DX9100Server Side Connection Descriptors Configuring the FieldServer as a Metasys N2 ServerServer Side Node Descriptors Driver Specific Map Descriptor Parameters Map Descriptor Example FS-8700-19MetasysN2 Driver Manual Appendix A.2. Managing Analog Inputs and Outputs for DX9100 Appendix B.3. Tip on Overrides Appendix B.2. Offline BehaviorFS-8700-19MetasysN2 Driver Manual FS-8700-19MetasysN2 Driver Manual Appendix C.2. Hardware connections Appendix C.3. Configuration SettingsFS-8700-19MetasysN2 Driver ManualPage 26 SUP UnitMNT DiagPmopt PmtypPMF1 PMF2PMK33 PMK32PMK34 PMOU1DO@ DOTFB@ DOF@XTLOA6 XTHIA6XTHIA7 XTLOA7FS-8700-19MetasysN2 Driver Manual DEC HEX Appendix D.2. Metasys DC9100 Memory MapTYPE1 TYPE3 TYPE6 TYPE8 LR1 HR1HR2 LR2OSZT@ OsoptOSOT@ OSSP@Appendix D.3. Metasys TC9100 Memory Map ROS DO6 Triac DO7 DO1 DO2Mods ModtRAS LSCIAS AFMPM5K2 PM5TYPPM5K3 PM5K4OCN4 OCO3OCO4 OCN5TCS3 TCS2TCS1 HDW1FTC1 LRI1OFS1 IOP1FSP FT@Fdif LOODST2 DST1DST3 DST4DST5 DST6DST7 Error Message Description and Action Appendix E. Error MessagesThis page Intentionally Left Blank