| Page 40 of 51 |
Appendix D.3. Metasys TC9100 Memory Map
Note: The TC9100 is not currently supported by the FieldServer MetasysN2 Driver. The information below is for interest and future use only.
General dynamic Parameters
Relative Item | Signal Condition | Read/Write | Johnson Tag | Description |
| |
0 | Byte | Read | UNIT | Device model. For | ||
1 | FP | Write | AI1 | Process Temperature | ||
2 | FP | Write | AI2 | Remote Temperature Set Point Bias | ||
3 | FP | Write | AI3 | Pressure |
| |
4 | FP | Write | AI4 | Override Input |
| |
5 |
|
|
| Spare |
|
|
6 |
|
|
| Spare |
|
|
7 |
|
|
| Spare |
|
|
8 |
|
|
| Spare |
|
|
9 | Word | Read | ADC | Selected Analog Input ADC counter | ||
10 | FP | Write | OCM1 | Output Programmable Module #1 | ||
11 | FP | Write | OCM2 | Output Programmable Module #2 | ||
12 | FP | Write | OCM3 | Output Programmable Module #3 | ||
13 | FP | Write | OCM4 | Output Programmable Module #4 | ||
14 | FP | Write | OCM5 | Output Programmable Module #5 | ||
15 | FP | Write | OCM6 | Output Programmable Module #6 | ||
16 | FP | Write | WSP1 | Working Set Point Control Module 1 | ||
17 | FP | Write | WSP2 | Working Set Point Control Module 2 | ||
18 | FP | Write | WSP3 | Working Set Point Control Module 3 | ||
19 | FP | Write | WSP4 | Working Set Point Control Module 4 | ||
20 | FP | Write | WSP5 | Working Set Point Control Module 5 | ||
21 | FP | Write | WSP6 | Working Set Point Control Module 6 | ||
22 | FP | Write | XAI1 | External Analog Input 1 | ||
23 | FP | Write | XAI2 | External Analog Input 2 | ||
24 | FP | Write | XAI3 | External Analog Input 3 | ||
25 | FP | Write | XAI4 | External Analog Input 4 | ||
26 | FP | Write | ACO5 | Analog Constant 5 | ||
27 | FP | Write | ACO6 | Analog Constant 6 | ||
28 | FP | Read | WAC | Winter Authority Correction | ||
29 | FP | Read | SAC | Summer Authority Correction | ||
30 | Word | Read | ALR | Analog Inputs Alarm Status | ||
| W(1) |
| AIH1 | Analog | Input | 1 High alarm |
| W(2) |
| AIL1 | Analog | Input | 1 High alarm |
| W(3) |
| AIH2 | Analog | Input | 2 High alarm |
| W(4) |
| AIL2 | Analog | Input | 2 Low alarm |
| W(5) |
| AIH3 | Analog | Input | 3 High alarm |
| W(6) |
| AIL3 | Analog | Input | 3 Low alarm |
| W(7) |
| AIH4 | Analog | Input | 4 High alarm |
| W(8) |
| AIL4 | Analog | Input | 4 Low alarm |
| W(9) |
|
| Not used |
| |
| W(10) |
|
| Not used |
| |
| W(11) |
|
| Not used |
| |
| W(12) |
|
| Not used |
| |
| W(13) |
|
| Not used |
| |
| W(14) |
|
| Not used |
| |
| W(15) |
|
| Not used |
| |
| W(16) |
|
| Not used |
| |
31 | Byte | Read | LOS | Logic Output Status | ||
| B(1) |
| DO3 | TRIAC | 3 ON |
|
| B(2) |
| DO4 | TRIAC | 4 ON |
|
| B(3) |
| DO5 | TRIAC | 5 ON |
|
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408)