Appendix D.2. Metasys DC9100 Memory Map

Note: The DC9100 is not currently supported by the FieldServer MetasysN2 Driver. The information below is for interest and future use only.

PAGE 0

Item

Item

 

Signal Condition

Read/Write

Johnson

Description

 

DEC

HEX

 

Tag

 

 

 

 

 

 

0

 

0

Byte

Read

MODL

Device model. Value always either 2 or

 

12

 

 

 

 

 

 

 

 

1

 

1

FP

Read

INP1

Analog input 1

2

 

2

FP

Read

INP2

Analog input 2

3

 

3

FP

Read

INP3

Analog input 3

4

 

4

FP

Read

INP4

Analog input 4

5

 

5

FP

Read

INP5

Analog input 5

6

 

6

FP

Read

INP6

Analog input 6

7

 

7

FP

Read

INP7

Analog input 7

8

 

8

FP

Read

INP8

Analog input 8

9

 

9

FP

Read

NCM1

Numeric calculation modul result

10

A

 

FP

Read

NCM2

Numeric calculation modul result

11

B

 

FP

Read

NCM3

Numeric calculation modul result

12

C

 

FP

Read

NMC4

Numeric calculation modul result

13

D

 

FP

Write

REC1

Remote constant 1

14

E

 

FP

Write

REC2

Remote constant 2

15

F

 

FP

Write

REC3

Remote constant 3

16

 

10

FP

Write

REC4

Remote constant 4

17

 

11

FP

Write

OUT1

Control output 1

18

 

12

FP

Write

OUT2

Control output 2

19

 

13

FP

Write

OUT3

Control output 3

20

 

14

FP

Write

OUT4

Control output 4

21

 

15

FP

Write

OUT5

Control output 5

22

 

16

FP

Write

OUT6

Control output 6

23

 

17

FP

Write

OUT7

Control output 7

24

 

18

FP

Write

OUT8

Control output 8

25

 

19

FP

Write

WSP1

Working setpoint 1

26

1A

 

FP

Write

WSP2

Working setpoint 2

27

1B

 

FP

Write

WSP3

Working setpoint 3

28

1C

 

FP

Write

WSP4

Working setpoint 4

29

1D

 

FP

Write

WSP5

Working setpoint 5

30

1E

 

FP

Write

WSP6

Working setpoint 6

31

1F

 

FP

Write

WSP7

Working setpoint 7

32

 

20

FP

Write

WSP8

Working setpoint 8

33

 

21

Word

Read

STW1

Status word 1

34

 

22

Word

Read

STW2

Status word 2

35

 

23

Word

Read

STW3

Status word 3

36

 

24

Word

Read

STW4

Status word 4

37

 

25

Word

Read

STW5

Status word 5

38

 

26

Word

Read

STW6

Status word 6

39

 

27

Word

Read

STW7

Status word 7

40

 

28

Word

Read

STW8

Status word 8

41

 

29

Word

Write

DOUT

Logic output DDC control

42

2A

 

Byte

Write

CHLD

Hold mode control

43

2B

 

Byte

Write

COMP

Supervisory mode control

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 33
Contents FS-8700-19 Metasys N2 Table of Contents Metasys N2 Description Required 3rd Party Configuration Provided by the Supplier of 3rd Party Equipment HardwareRequired 3rd Party Software Hardware Connection Tips / Hints Hardware ConnectionsData Arrays/Descriptors Configuring the FieldServer as a Metasys N2 ClientClient Side Connection Descriptions Client Side Node Descriptors AI, AO, DI, do Object Configuration VMA Map Descriptor Parameters ADF ADI Timing Parameters 2.3. DX9100 Map Descriptor ParametersMap Descriptor Example 2 VMA Map Descriptor Example 1 N2OpenDAAO3 Wrbx Map Descriptor Example 3 DX9100Server Side Connection Descriptors Configuring the FieldServer as a Metasys N2 ServerServer Side Node Descriptors Driver Specific Map Descriptor Parameters Map Descriptor Example FS-8700-19MetasysN2 Driver Manual Appendix A.2. Managing Analog Inputs and Outputs for DX9100 Appendix B.3. Tip on Overrides Appendix B.2. Offline BehaviorFS-8700-19MetasysN2 Driver Manual FS-8700-19MetasysN2 Driver Manual Appendix C.2. Hardware connections Appendix C.3. Configuration SettingsFS-8700-19MetasysN2 Driver ManualPage 26 SUP UnitMNT DiagPmopt PmtypPMF1 PMF2PMK33 PMK32PMK34 PMOU1DO@ DOTFB@ DOF@XTLOA6 XTHIA6XTHIA7 XTLOA7FS-8700-19MetasysN2 Driver Manual DEC HEX Appendix D.2. Metasys DC9100 Memory MapTYPE1 TYPE3 TYPE6 TYPE8 LR1 HR1HR2 LR2OSZT@ OsoptOSOT@ OSSP@Appendix D.3. Metasys TC9100 Memory Map ROS DO6 Triac DO7 DO1 DO2Mods ModtRAS LSCIAS AFMPM5K2 PM5TYPPM5K3 PM5K4OCN4 OCO3OCO4 OCN5TCS3 TCS2TCS1 HDW1FTC1 LRI1OFS1 IOP1FSP FT@Fdif LOODST2 DST1DST3 DST4DST5 DST6DST7 Error Message Description and Action Appendix E. Error MessagesThis page Intentionally Left Blank