FieldServer FS-8704-49 Driver Related Map Descriptor Parameters, Timing Parameters

Page 10

FS-8700-49_Data_Aire_DAP

Page 10 of 48

4.4.2.Driver Related Map Descriptor Parameters

Column Title

Function

Legal Values

 

Name of Node to fetch data

One of the node names

Node_Name

specified in “Client Node

from

 

Descriptor” above

 

 

Data_Type

Data type

Register, Coil, AI, DI

 

 

 

Length

Length of Map Descriptor

1

 

 

Not required for client

Address

Starting address of read block

configuration - used in

 

 

simulation configuration only.

 

Only required when the function

 

 

is a Read (rdbc).

 

 

Tells the driver to poll the

 

DA_Func*

device for all the data that is

Everything – See Appendix A

available. The data is device

 

 

 

specific.

 

 

Other uses of this parameter

 

 

are discussed in Appendix B .

 

 

Required when the function is a

 

 

write (wrbc) or when the Map

 

 

Descriptor is associated with a

 

 

write by means of the

 

DA_Field

DA_Assoc parameter value.

See Appendix A.2 for a list of

This is the name of the data

permitted values.

 

 

field whose value you wish to

 

 

set in the device.

 

 

Other uses of this parameter

 

 

are discussed in Appendix B.

 

 

Use to associate passive Map

 

 

Descriptors with an active Map

 

 

Descriptor. Multiple fields can

Any positive integer. See

DA_Assoc

be associated with one WRBC

Appendix E

 

Map Descriptor, thus writing

 

 

 

multiple values to one device

 

 

using just one message.

 

4.4.3.Timing Parameters

Column Title

Function

Legal Values

Scan_Interval

Rate at which data is polled

≥0.1s

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com

Image 10
Contents FS-8704-49 Data Aire DAP Table of Contents Page Data Alarm Network Module Network LED Operation Performance Issues Dartiii onlyData Aire Description FS-8700-49DataAireDAP Hardware Connections ModelConfiguring the FieldServer as a Data Aire Client Data Arrays/DescriptorsClient Side Connection Descriptions DAPClient Side Node Descriptors Driver Related Map Descriptor Parameters Timing ParametersMap Descriptor Example 1 Everything Map Descriptor Example 2 Writing a Set-PointAdditional information is provided in Appendix B UnitType 185 499 855 908 Appendix A.2. Data Point Descriptions Runtimec1 Compressor 1 runtime DAP-Xtra All Adjrate Adjustment rate DAP Menu DAP049,048,046 DAP80 Dcalib Discharge Air sensor DAP80 Menu Valveconfig Chilled water Valve DAP80 Menu FS-8700-49DataAireDAP Appendix A.3. Data Unit Types FS-8700-49DataAireDAP Appendix B.2. DAFunc Parameter Permitted values Appendix B.3. DAField Parameter Permitted values4 Appendix B.4. DAMethod Parameter Values and NotesFS-8700-49DataAireDAPPage 29 DAAI1 Rdbc FS-8700-49DataAireDAPPage 31 INH04 DAWR01 Appendix C.2. Dead Nodes Appendix C. Troubleshooting Tips Appendix C.1. Bad ValuesAppendix C.7. Wiring Appendix C.3. NoiseAppendix C.8. Stuck Unit Appendix C.9. Number of UnitsAppendix D. Error Messages Page Page Appendix D.1. Exposing Driver Statistics FYIPage Appendix E.2. Associated Map Descriptors Appendix E.4. DAP Unit Errors Appendix E.3. Starting/Stopping DAP devicesFS-8700-49DataAireDAP FS-8700-49DataAireDAP FS-8700-49DataAireDAP FS-8700-49DataAireDAP Dasetpoints Wrbc Appendix F. Write Through’s This page Intentionally Left Blank