Appendix E.3. Starting/Stopping DAP devices

The DAP-Config command is an exception to the above notes. A read is not required. The DAP Config command is used to turn off/on DAP units. The Command uses two consecutive array elements. The first is the zone, the second is the inhibit command. Valid zones are 0-63.

If any inhibit bit (bits 0-5) is set then the unit will not run. If bits 0 to 5 are off then the unit will run. Bits 6& 7 are used for display only on the DAP panel.

0x01 - Inhibit Cooling

0x02 - Inhibit Heating

0x04 - Inhibit Humid

0x08 - Inhibit Dehumidification

0x10 - Inhibit fan

0x20 - Reserved

0x40 - Network Standby - Display on panel (only has no effect on unit) 0x80 - Network off inhibit is active - display only - no effect on operation

This function should be used as a wrbc/x. When the driver encounters this command it reads the associated Data Array, loads the two elements found at the array offset into the message and transmits the message. The driver does not set any Data Array elements to confirm that the command concluded successfully.

Additional information is provided in Appendix B.10

Appendix E.4. DAP Unit Errors

Dap-Stat Query

The following table provides information on the storage of errors obtained in response to the Dap-Stat Query. Note that the errors are stored two ways – One storage method stores 8 alarm bits at a time in a single array element (stored as byte values) – The other method stores each alarm at a different location in the Data Array.

 

 

 

Location in

Location in Data

 

 

 

 

 

Data Array

Array (Absolute

 

 

Byte

Bit

Relative

(Absolute

Offset) Each set

046, 048 and 049 Units

DAP 80 Units

 

 

Offset

Offset) Each

of 8 alarms

 

 

 

 

 

alarm stored as

stored as a

 

 

 

 

 

a separate bit

byte*

 

 

 

 

 

 

 

 

Manual Override:

0

0

0

73

44:00

N/A

check bypass switch

( DapII ver 5.0 or

 

 

 

 

 

 

 

 

 

 

 

 

later)

 

 

 

 

 

High Pressure Failure

Water detected

0

1

1

74

44:01

under floor: check

Compressor No. 1

 

 

 

 

 

probe

 

 

 

 

 

 

0

2

2

75

44:02

High Pressure Failure

No air flow: check

Compressor No. 2

belt and motor

 

 

 

 

 

0

3

3

76

44:03

High Pressure Failure

Dirty filter: check

Compressor No. 3

filters

 

 

 

 

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com

Image 41
Contents FS-8704-49 Data Aire DAP Table of Contents Page Data Aire Description Performance Issues Dartiii onlyData Alarm Network Module Network LED Operation FS-8700-49DataAireDAP Model Hardware ConnectionsData Arrays/Descriptors Configuring the FieldServer as a Data Aire ClientDAP Client Side Connection DescriptionsClient Side Node Descriptors Timing Parameters Driver Related Map Descriptor ParametersMap Descriptor Example 2 Writing a Set-Point Map Descriptor Example 1 EverythingAdditional information is provided in Appendix B UnitType 185 499 855 908 Appendix A.2. Data Point Descriptions Runtimec1 Compressor 1 runtime DAP-Xtra All Adjrate Adjustment rate DAP Menu DAP049,048,046 DAP80 Dcalib Discharge Air sensor DAP80 Menu Valveconfig Chilled water Valve DAP80 Menu FS-8700-49DataAireDAP Appendix A.3. Data Unit Types FS-8700-49DataAireDAP Appendix B.2. DAFunc Parameter Permitted values Appendix B.4. DAMethod Parameter Values and Notes Appendix B.3. DAField Parameter Permitted values4FS-8700-49DataAireDAPPage 29 DAAI1 Rdbc FS-8700-49DataAireDAPPage 31 INH04 DAWR01 Appendix C.7. Wiring Appendix C. Troubleshooting Tips Appendix C.1. Bad ValuesAppendix C.2. Dead Nodes Appendix C.3. NoiseAppendix C.9. Number of Units Appendix C.8. Stuck UnitAppendix D. Error Messages Page Page FYI Appendix D.1. Exposing Driver StatisticsPage Appendix E.2. Associated Map Descriptors Appendix E.3. Starting/Stopping DAP devices Appendix E.4. DAP Unit ErrorsFS-8700-49DataAireDAP FS-8700-49DataAireDAP FS-8700-49DataAireDAP FS-8700-49DataAireDAP Dasetpoints Wrbc Appendix F. Write Through’s This page Intentionally Left Blank