FieldServer FS-8704-49 instruction manual Additional information is provided in Appendix B

Page 12

FS-8700-49_Data_Aire_DAP

Page 12 of 48

4.4.6.Map Descriptor: Example 3 – Writing multiple points using one message.

Additional information is provided in Appendix B

// Client Side Map Descriptors

Map Descriptors

 

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

Address,

Length,

DA_Field,

DA_Assoc,

Scan_Interval

Write_Map Descriptor_1,

DA_SETPOINTS,

0,

WRBC,

Unit1,

0,

1,

nom_h_setpt,

2,

120s

Write_Map Descriptor_1,

DA_SETPOINTS,

1,

passive,

Unit1,

0,

1,

t_setpt,

2,

 

 

 

 

 

 

 

 

 

 

 

A 'Write' and a passive to the same node. This write will update two fields, the nom_h_setpt and the t_setpt. The write Map Descriptor. must precede the passive. For a Dart, use wrbx instead of wrbc.

Associate the passive Map Descriptor to the active (wrbc) Map Descriptor. In this way the driver will use only one message to write to the device. The message will be built using both Map Descriptors. This method reduces the communication load.

The association is made using the DA_Assoc parameter. Use unique positive integers. Omitting the DA_Assoc parameter when using ‘passive’ Map Descriptors will produce ambiguous results.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com

Image 12
Contents FS-8704-49 Data Aire DAP Table of Contents Page Performance Issues Dartiii only Data Alarm Network Module Network LED OperationData Aire Description FS-8700-49DataAireDAP Hardware Connections ModelConfiguring the FieldServer as a Data Aire Client Data Arrays/DescriptorsClient Side Connection Descriptions DAPClient Side Node Descriptors Driver Related Map Descriptor Parameters Timing ParametersMap Descriptor Example 1 Everything Map Descriptor Example 2 Writing a Set-PointAdditional information is provided in Appendix B UnitType 185 499 855 908 Appendix A.2. Data Point Descriptions Runtimec1 Compressor 1 runtime DAP-Xtra All Adjrate Adjustment rate DAP Menu DAP049,048,046 DAP80 Dcalib Discharge Air sensor DAP80 Menu Valveconfig Chilled water Valve DAP80 Menu FS-8700-49DataAireDAP Appendix A.3. Data Unit Types FS-8700-49DataAireDAP Appendix B.2. DAFunc Parameter Permitted values Appendix B.3. DAField Parameter Permitted values4 Appendix B.4. DAMethod Parameter Values and NotesFS-8700-49DataAireDAPPage 29 DAAI1 Rdbc FS-8700-49DataAireDAPPage 31 INH04 DAWR01 Appendix C. Troubleshooting Tips Appendix C.1. Bad Values Appendix C.7. WiringAppendix C.2. Dead Nodes Appendix C.3. NoiseAppendix C.8. Stuck Unit Appendix C.9. Number of UnitsAppendix D. Error Messages Page Page Appendix D.1. Exposing Driver Statistics FYIPage Appendix E.2. Associated Map Descriptors Appendix E.4. DAP Unit Errors Appendix E.3. Starting/Stopping DAP devicesFS-8700-49DataAireDAP FS-8700-49DataAireDAP FS-8700-49DataAireDAP FS-8700-49DataAireDAP Dasetpoints Wrbc Appendix F. Write Through’s This page Intentionally Left Blank