| Location in | Location in Data |
|
|
|
|
|
|
| Data Array | Array (Absolute |
|
|
|
| Byte | Bit | Relative | (Absolute | Offset) Each set | 046, 048 and 049 Units | DAP 80 Units | |
|
|
| Offset | Offset) Each | of 8 alarms |
|
|
|
|
|
|
| alarm stored as | stored as a |
|
|
|
|
|
|
| a separate bit | byte* |
|
|
|
| 3 | 0 | 24 | 97 | 46:00 | Low air temperature | Local alarm #1: See | |
| warning | tag inside door | ||||||
|
|
|
|
|
| |||
| 3 | 1 | 25 | 98 | 46:01 | High air temperature | Local alarm #2: See | |
| warning | tag inside door | ||||||
|
|
|
|
|
| |||
| 3 | 2 | 26 | 99 | 46:02 | Low Humidity warning | Local alarm #3: See | |
| tag inside door | |||||||
|
|
|
|
|
|
| ||
| 3 | 3 | 27 | 100 | 46:03 | High Humidity warning | Local alarm #4: See | |
| tag inside door | |||||||
|
|
|
|
|
|
| ||
| 3 | 4 | 28 | 101 | 46:04 | Low | Standby pump on: | |
| check primary pump | |||||||
|
|
|
|
|
| High | UPS power on: | |
| 3 | 5 | 29 | 102 | 46:05 | check main power | ||
| alarm | |||||||
|
|
|
|
|
| supply | ||
|
|
|
|
|
|
| ||
| 3 | 6 | 30 | 103 | 46:06 | Low | Custom message on | |
| alarm | optional input #1 | ||||||
|
|
|
|
|
| |||
| 3 | 7 | 31 | 104 | 46:07 | High | Custom message on | |
| alarm | optional input #2 | ||||||
|
|
|
|
|
| |||
| 4 | 0 | 32 | 105 | 47:00 | High or Low limits | Custom message on | |
| misadjusted | optional input #3 | ||||||
|
|
|
|
|
| |||
| 4 | 1 | 33 | 106 | 47:01 | Air temperature sensor | Custom message on | |
| error | optional input #4 | ||||||
|
|
|
|
|
| |||
| 4 | 2 | 34 | 107 | 47:02 | Humidity sensor error | Humidification | |
| Inhibited | |||||||
|
|
|
|
|
|
| ||
| 4 | 3 | 35 | 108 | 47:03 | Discharge air sensor error | Reheat inhibited | |
|
|
|
|
|
| No communications with | Reheat and | |
| 4 | 4 | 36 | 109 | 47:04 | humidification | ||
|
|
|
|
|
| temp/humid module | inhibited | |
|
|
|
|
|
|
| ||
|
|
|
|
|
| No communications with | Discharge air | |
| 4 | 5 | 37 | 110 | 47:05 | temperature limit | ||
|
|
|
|
|
| LCD module | (just a condition) | |
|
|
|
|
|
|
| ||
|
|
|
|
|
| Alarm network | Reheat mode during | |
| 4 | 6 | 38 | 111 | 47:06 | dehumidification | ||
| communications failure | |||||||
|
|
|
|
|
| (just a condition) | ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| Manual Override: | |
| 4 | 7 | 39 | 112 | 47:07 | AC Power or controller | Check bypass | |
| restart | switches (DAPII ver | ||||||
|
|
|
|
|
| |||
|
|
|
|
|
|
| 5.1 and later) | |
| 5 | 0 | 40 | 113 | 48:00 | Network doppelganger | N/A | |
| error | |||||||
|
|
|
|
|
|
|
| |
| 5 | 1 | 41 | 114 | 48:01 | Incompatible Fahrenheit / | N/A | |
|
|
|
|
|
| centigrade mode |
|
|
| 5 | 2 | 42 | 115 | 48:02 | Schedule normal | N/A | |
| maintenance due | |||||||
|
|
|
|
|
|
|
| |
| 5 | 3 | 43 | 116 | 48:03 | compressor short cycle | N/A | |
| warning | |||||||
|
|
|
|
|
|
|
| |
| 5 | 4 | 44 | 117 | 48:04 | Fan motor overload, | N/A | |
| check motor amperage | |||||||
|
|
|
|
|
|
|
|
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com Tel: (408)