FieldServer FS-8704-49 instruction manual FS-8700-49DataAireDAPPage 29

Page 29

FS-8700-49_Data_Aire_DAPPage 29 of 48

Appendix B.5. Advanced Map Descriptor 1:Collecting Data From Multiple Fileds

// Client Side Nap Descriptors

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

Address,

Length,

DA_Func,

DA_Field,

Scan_Interval

A1,

DA_AI3,

0,

RDBC

Node_A,

0,

1,

dap-stat,

temp,

5

A2,

DA_AI3,

1,

passive,

Node_A,

0,

1,

dap-stat,

hum,

5

A3,

DA_AI3,

2,

passive,

Node_A,

0,

1,

dap-stat,

d_temp,

5

A4,

DA_AI3,

3,

passive,

Node_A,

0,

1,

dap-stat,

hiTemp,

5

A5,

DA_AI3,

4,

passive,

Node_A,

0,

1,

dap-stat,

loTemp,

5

A6,

DA_AI2,

0,

passive,

Node_A,

0,

1,

dap-stat,

cs_on,

5

A7,

DA_AI2,

1,

passive,

Node_A,

0,

1,

dap-stat,

hs_on,

5

 

 

 

 

 

 

 

 

 

 

It would be sensible for DA_AI3 to be an array of FLOATs because the temps and humidity’s return real numbers with one digit after the decimal point.

DA_AI2 could be any type of array other than BIT because the values returned for these parameters are whole numbers less than 255.

All these Map Descriptors address Node_A therefore only one Map Descriptor needs to read (rdbc) the node. The remaining Map Descriptors can be passive (thus optimizing communications.)

All these Map

Server is a

The scan time

Descriptors

DAP reading

is only

read their data

status

important for

from the same

information.

the active Map

Server

 

 

Descriptor.

 

 

These parameters must be typed in exactly as specified in this manual. They are case sensitive. The format of the data extracted depends on the parameter.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com

Image 29
Contents FS-8704-49 Data Aire DAP Table of Contents Page Data Aire Description Performance Issues Dartiii onlyData Alarm Network Module Network LED Operation FS-8700-49DataAireDAP Model Hardware ConnectionsData Arrays/Descriptors Configuring the FieldServer as a Data Aire ClientDAP Client Side Connection DescriptionsClient Side Node Descriptors Timing Parameters Driver Related Map Descriptor ParametersMap Descriptor Example 2 Writing a Set-Point Map Descriptor Example 1 EverythingAdditional information is provided in Appendix B UnitType 185 499 855 908 Appendix A.2. Data Point Descriptions Runtimec1 Compressor 1 runtime DAP-Xtra All Adjrate Adjustment rate DAP Menu DAP049,048,046 DAP80 Dcalib Discharge Air sensor DAP80 Menu Valveconfig Chilled water Valve DAP80 Menu FS-8700-49DataAireDAP Appendix A.3. Data Unit Types FS-8700-49DataAireDAP Appendix B.2. DAFunc Parameter Permitted values Appendix B.4. DAMethod Parameter Values and Notes Appendix B.3. DAField Parameter Permitted values4FS-8700-49DataAireDAPPage 29 DAAI1 Rdbc FS-8700-49DataAireDAPPage 31 INH04 DAWR01 Appendix C.7. Wiring Appendix C. Troubleshooting Tips Appendix C.1. Bad ValuesAppendix C.2. Dead Nodes Appendix C.3. NoiseAppendix C.9. Number of Units Appendix C.8. Stuck UnitAppendix D. Error Messages Page Page FYI Appendix D.1. Exposing Driver StatisticsPage Appendix E.2. Associated Map Descriptors Appendix E.3. Starting/Stopping DAP devices Appendix E.4. DAP Unit ErrorsFS-8700-49DataAireDAP FS-8700-49DataAireDAP FS-8700-49DataAireDAP FS-8700-49DataAireDAP Dasetpoints Wrbc Appendix F. Write Through’s This page Intentionally Left Blank