FieldServer FS-8704-49 instruction manual Appendix C.8. Stuck Unit, Appendix C.9. Number of Units

Page 34

FS-8700-49_Data_Aire_DAP

Page 34 of 48

Appendix C.8. Stuck Unit.

Communications on the DAP units requires the operation of a mechanical relay. This can get stuck. The Front Panel menu of each DAP unit allows a user to execute a diagnostic test of the comms board. The customer should execute this test and use the Data Aire installation guide to resolve any issues. Typically a failed unit requires replacement. A single failed card will fail the whole network. The FieldServer sends polls on the primary port and expects responses on the secondary port. The fact that we get back a copy of the poll message on the secondary port does not mean that the units are operating correctly since this is possible when the units are stuck in pass thru mode.

Appendix C.9. Number of Units

Up to 250 DAP devices can be connected to a FieldServer using the DAP driver.

Normal RS485 network considerations apply - these limit the number of units based on the load of each node.

For unit loads only 32 devices per network can be used.

For .25 unit loads 128 devices can be used on one network segment. If more than 32 full unit loads are required then the network must be segmented and connected via a repeater

It may be necessary to use a repeater if total RS-485 length exceeds 1000ft.

It is recommended that tests are performed with a single or few units.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com

Image 34
Contents FS-8704-49 Data Aire DAP Table of Contents Page Data Alarm Network Module Network LED Operation Performance Issues Dartiii onlyData Aire Description FS-8700-49DataAireDAP Hardware Connections ModelConfiguring the FieldServer as a Data Aire Client Data Arrays/DescriptorsClient Side Connection Descriptions DAPClient Side Node Descriptors Driver Related Map Descriptor Parameters Timing ParametersMap Descriptor Example 1 Everything Map Descriptor Example 2 Writing a Set-PointAdditional information is provided in Appendix B UnitType 185 499 855 908 Appendix A.2. Data Point Descriptions Runtimec1 Compressor 1 runtime DAP-Xtra All Adjrate Adjustment rate DAP Menu DAP049,048,046 DAP80 Dcalib Discharge Air sensor DAP80 Menu Valveconfig Chilled water Valve DAP80 Menu FS-8700-49DataAireDAP Appendix A.3. Data Unit Types FS-8700-49DataAireDAP Appendix B.2. DAFunc Parameter Permitted values Appendix B.3. DAField Parameter Permitted values4 Appendix B.4. DAMethod Parameter Values and NotesFS-8700-49DataAireDAPPage 29 DAAI1 Rdbc FS-8700-49DataAireDAPPage 31 INH04 DAWR01 Appendix C.2. Dead Nodes Appendix C. Troubleshooting Tips Appendix C.1. Bad ValuesAppendix C.7. Wiring Appendix C.3. NoiseAppendix C.8. Stuck Unit Appendix C.9. Number of UnitsAppendix D. Error Messages Page Page Appendix D.1. Exposing Driver Statistics FYIPage Appendix E.2. Associated Map Descriptors Appendix E.4. DAP Unit Errors Appendix E.3. Starting/Stopping DAP devicesFS-8700-49DataAireDAP FS-8700-49DataAireDAP FS-8700-49DataAireDAP FS-8700-49DataAireDAP Dasetpoints Wrbc Appendix F. Write Through’s This page Intentionally Left Blank