FieldServer FS-8704-49 instruction manual

Page 36

FS-8700-49_Data_Aire_DAP

Page 36 of 48

 

 

 

 

 

Message

Description

Discussion

 

 

Map Descriptor= <%s>

permitted.5

 

 

Err. Invalid Daire

 

 

DAP:#11

function (%d) .Map

The value of the DA_Function parameter specified in

 

 

Descriptor= <%s>

 

 

the CSV file cannot be recognized by the driver. Read

 

 

Err: Invalid Daire field

 

 

6

 

DAP:#12

(%d) .Map Descriptor=

Appendix B.2 for more information.

 

 

<%s>

 

 

 

Err. Invalid Daire

The value of the DA_Method parameter specified in the

 

DAP:#13

method (%d) .Map

CSV file cannot be recognized by the driver. Read

 

 

Descriptor= <%s>

Appendix B.4 for more information.6

 

 

Err. Map Desc. Cant

The value of the DA_Function parameter specified in

 

DAP:#14

understand function=

the CSV file cannot be recognized by the driver. Read

 

 

%d <%s>

Appendix B.2 for more information.6

 

 

Err. Map Desc. Cant

The value of the DA_Field parameter specified in the

 

DAP:#15

understand id= %d

CSV file cannot be recognized by the driver. Read

 

 

<%s>

Appendix B.3 for more information. 6

 

DAP:#16

Err. Unknown

 

 

Response= %X( h)

A message has been received that cannot be

 

 

 

DAP:#17

Err. Unknown Query

recognized. If this error occurs repeatedly, make a log

 

DAP:#18

Err. Unknown

file and report the error to FST. If the error occurs

 

Command

occasionally it may be indicating an occasional corrupt

 

 

 

DAP:#19

Err. Unknown Msg

message and may be ignored.

 

Type

 

 

 

 

 

DAP:#20

Writing before Unit

If you see this message printed report the fact to FST

 

Type is known.

immediately.

 

 

 

 

Err. Cant write this

Only certain data is writable. See Section Appendix A.2

 

DAP:#21

function= %c. Map

 

for more information.5

 

 

Descriptor= <%s>

 

 

 

 

It is not possible to write to a DAP device before it has

 

 

 

been read successfully. This message arises if the

 

 

FYI. Write abandoned.

device has been read but some data contained in the

 

DAP:#22

Map Descriptor=<%s>.

read is invalid. The driver is preventing the invalid data

 

ch=%d j=%d off=%d

being written back to the device. If this message only

 

 

 

 

dev=<%s>

occurs once or twice after the FieldServer is restarted, it

 

 

 

may be ignored. If the message occurs repeatedly then

 

 

 

take a log file and report the error to FST

 

 

 

It isn’t possible to write to a DAP device before it has

 

 

FYI. Write abandoned.

been read successfully. If this message only occurs

 

DAP:#23

Read incomplete. Will

once or twice after the FieldServer is restarted, it may

 

DAP:#23a

retry. Map Descriptor=

safely be treated as for information only. If the message

 

 

<%s>

occurs repeatedly then the configuration may need

 

 

 

changing.

 

DAP:#24

Err. Rev-Translate:

Report this error to FST providing a copy of your CSV

 

Unknown Method.

file.

 

 

6Edit the CSV file and reset the FieldServer for the changes to take effect.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com

Image 36
Contents FS-8704-49 Data Aire DAP Table of Contents Page Performance Issues Dartiii only Data Alarm Network Module Network LED OperationData Aire Description FS-8700-49DataAireDAP Hardware Connections ModelConfiguring the FieldServer as a Data Aire Client Data Arrays/DescriptorsClient Side Connection Descriptions DAPClient Side Node Descriptors Driver Related Map Descriptor Parameters Timing ParametersMap Descriptor Example 1 Everything Map Descriptor Example 2 Writing a Set-PointAdditional information is provided in Appendix B UnitType 185 499 855 908 Appendix A.2. Data Point Descriptions Runtimec1 Compressor 1 runtime DAP-Xtra All Adjrate Adjustment rate DAP Menu DAP049,048,046 DAP80 Dcalib Discharge Air sensor DAP80 Menu Valveconfig Chilled water Valve DAP80 Menu FS-8700-49DataAireDAP Appendix A.3. Data Unit Types FS-8700-49DataAireDAP Appendix B.2. DAFunc Parameter Permitted values Appendix B.3. DAField Parameter Permitted values4 Appendix B.4. DAMethod Parameter Values and NotesFS-8700-49DataAireDAPPage 29 DAAI1 Rdbc FS-8700-49DataAireDAPPage 31 INH04 DAWR01 Appendix C. Troubleshooting Tips Appendix C.1. Bad Values Appendix C.7. WiringAppendix C.2. Dead Nodes Appendix C.3. NoiseAppendix C.8. Stuck Unit Appendix C.9. Number of UnitsAppendix D. Error Messages Page Page Appendix D.1. Exposing Driver Statistics FYIPage Appendix E.2. Associated Map Descriptors Appendix E.4. DAP Unit Errors Appendix E.3. Starting/Stopping DAP devicesFS-8700-49DataAireDAP FS-8700-49DataAireDAP FS-8700-49DataAireDAP FS-8700-49DataAireDAP Dasetpoints Wrbc Appendix F. Write Through’s This page Intentionally Left Blank