Chatsworth Products user manual RIM-600 Manual

Page 30

RIM-600 Manual

Step 5) Remove all of the screws in the top cover. Carefully remove the top cover.

Step 6) Locate the battery on the right side. There will be a red wire (positive)

and a black wire (negative) connected to the battery. Using needle nose pliers, remove the connector with the black wire from the battery first. Gently wiggle it off.

Step 7) Using needle nose pliers, remove the connector with the red wire from the battery.

Step 8) Using the nut driver, remove the four nuts which hold down the battery bracket. Remove the bracket and battery.

Step 9) Install the new battery and replace the bracket.

Step 10) Attach the connector with the red wire to the positive terminal of the battery.

Step 11) Attach the connector with the black wire to the negative terminal of the battery.

Step 12) Replace the top RIM-600 cover and secure with the screws.

Step 13) Re-install in rack.

Step 14) Re-attach the power cord.

Step 15) Re-connect the phone line.

Step 16) Turn the Power Switch back on.

30

Image 30
Contents Remote Infrastructure Management RIM-600 VersionPage Important Safety Instructions FCC Requirements Chatsworth Products, Inc Industrial Drive New Bern, NC FaxTelephone Consumer Protection Act Host only General Requirements for all Automatic Dialers Host onlyRIM-600 Manual Year Limited Warranty Chatsworth Products, Inc Industrial Drive New Bern, NC Fax Table of Contents RIM-600 Software RIM-600 Quick Start GuideConfiguring Templates Configuring IP Alarms IP Alarm Setup Software InstallationConfiguring Hosts and Nodes Setting Up An Enterprise Alarm LogicDeleting a Profile Contacts Adding Contacts Configuring User Profiles and Contacts Adding a ProfileHoliday Setup Alarm Message Pop-Ups WebSnmp Simple Network Management Protocol GraphsCommunicating with your RIM-600 RIM-600 PowerGate Specifications Operating Specifications PowerGatePowerGate2 PowerGate2 Setup via the RIM-600 ConsoleView SoftwareRIM-600 Sensors Room Humidity Sensor with display External Power SensorRoom Humidity Sensor Water Detection Sensor60051-001 4-20mA Bridge Door SwitchDry Contact Bridge Passive Infrared Detection SensorSmoke Detector Sensor Technical Support for the RIM-600 SensorsFeatures IntroductionTechnical Support Physical Description Host Installation and ConfigurationAbout This Manual Front Panel LayoutSensor Inputs ON/OFF Switch InstallationAC Power and Battery LEDs Rear PanelRack Mount Installation Wall Mount InstallationOperating Environment Tabletop Installation Power On Self Test PostConnecting Sensors Network Configuration Enterprise Status Unit Type IP Return to main menu Local Configuration Definitions Battery Maintenance Replacing the BatteryRIM-600 Manual Communications Specifications RIM-600 Host SpecificationsOperating Specifications Environmental MonitoringNode Installation & Configuration MicrophoneBattery Compartment Battery Replacement Battery replacement in the Node unitWall-mounted Node Unit RIM-600 Node Unit Local Configuration Definitions Node Specifications Default Username and Password Install Units and Configure Network SettingsInstall Software and Log In to Host RIM-600 Quick Start GuideConfigure the Unit Properties for the Host and Nodes Configure Input TemplatesConnect Environmental Sensors to Host and Nodes Configure User Profiles and Contacts Configure IP AlarmsRecord and Assign Voice Messages Installing from the CD Software Installation and Hardware RequirementsSoftware Installation Hardware and Software RequirementsConfiguring Hosts and Nodes Setting Up An EnterpriseStarting the RIM-600 ConsoleView Software Deleting a Host Connecting to a HostAdding a Host Adding an Enterprise GroupSetting the Unit Properties for the RIM-600 Host System Info tabClock settings tab Adding a NodeChanging Host Network Settings using ConsoleView Setting the Unit Properties for the NodeDeleting a Node Changing Node Network Settings Node Properties Setup TabConfiguring Environmental Inputs Channel SetupChannel Setup screen Editing the scheduleAlarm Class dropdown menu Alarm Response via the PowerGate, PowerGate2, or Camera Camera Snapshots on AlarmHigh Sound Alarms Realtime Strip ChartConfiguring Templates Environmental Input Alarm LogicTrouble Alarms Removing/Changing a SensorTemplate Types Configuring IP Alarms IP Alarm SetupProgramming Alarm Parameters IP Schedule screen Alarm Logic Removing an IP Alarm IP Alarm FlowchartInput/Alarm Classes Setup ClassesConfiguring User Profiles and Contacts Configuring User ProfilesAdding a Profile Master System Site Admin User PermissionsClasses Selecting ClassesContacts Deleting a ProfileAdding Contacts Voice Calls Numeric Pager CallsAlphanumeric Pager Calls Mail Alarm Delivery OptionsFax Calls ScheduleRecording and Uploading Voice Messages ReconnectingSaving and Loading Programming Recording Voice MessagesCustom Voice Manager Holiday Setup Holiday ListAlarm Message Pop-Ups Activating Alarm Pop-UpsEnabling Custom Pop-Up Messages Setting Pop-Up Text Location Audible Alarm NotificationEditing Pop-Up Custom Message Mail Setup and Two-Way E-Mail Commands Smtp Error messagesRequesting an IP Ping Two Way E-MailRequesting a Status Report Requesting a Trace RouteRequesting a PowerGate Outlet Command Requesting a Picture from a CameraRequesting Help Configuring a Video Camera PanasonicAssociating Cameras Web GraphsUpdating the Web Remote WebHistory Viewing the Remote WebDatalog History History OptionsViewing History History QuickViewQuerying the History Database with HistoryView Graphing Printing Data Exporting DataDeleting Data Manually Forcing History DownloadsCopying to the Clipboard ArchivingUpdating Firmware Manual Datalog Download in progress

RIM-600 specifications

Chatsworth Products (CPI) has established a reputation for delivering innovative solutions in the field of infrastructure technology. One of their standout products is the RIM-600, a versatile and feature-rich telecommunications rack designed to accommodate various IT equipment needs in data centers and network environments.

The RIM-600 boasts a robust construction, featuring a sturdy steel framework that enhances durability and provides optimal protection for sensitive electronic components. This product is engineered to support a range of IT gear, including servers, network switches, and patch panels, making it an ideal choice for organizations looking to maximize their data center efficiency.

One of the key features of the RIM-600 is its impressive cooling capability. The rack is designed with advanced airflow management in mind. It includes adjustable vertical cable management options that help maintain proper airflow while minimizing cable congestion. This design is crucial for preventing overheating and ensuring reliable performance for all housed equipment, thereby extending the lifespan of critical hardware.

The RIM-600 also incorporates tool-less assembly, simplifying the installation and setup process. This feature is particularly advantageous for IT professionals who require a rapid deployment of systems without cumbersome installation procedures. Furthermore, the rack’s modular design allows for easy customization and scalability, accommodating varying configurations as business needs evolve.

Moreover, the RIM-600 ensures enhanced accessibility with removable side panels and rear doors. This facilitates hassle-free cable access and promotes efficient maintenance practices. The inclusion of integrated grounding provisions ensures that all equipment remains secure and compliant with safety standards.

In terms of scalability, the RIM-600 can support up to 3,000 pounds of equipment, offering ample weight capacity for heavy-duty installations. Its compatibility with popular accessories, including shelving, power distribution units, and cooling solutions, further enhances the rack's utility and flexibility in diverse operational environments.

In summary, the Chatsworth Products RIM-600 is an exceptional telecommunications rack combining durability, cooling efficiency, and ease of installation. Its innovative design and thoughtful features make it a top choice for organizations looking to elevate their data center infrastructure while ensuring equipment protection and optimal performance.