CHAPTER 4
Identifying Parameter Defaults
For Carrier Drives
Use the following table to identify and set the parameter defaults for Carrier drives.
Important: Setting P.050 (Restore Defaults) to ON will restore the drive to Reliance defaults, not Carrier defaults. If this has been done, set the following parameters to restore Carrier defaults.
Parameter No. | Parameter Name | Setting | |
|
|
|
|
P.000 | Control Source | rE | |
|
|
|
|
P.001 | Accel Time 1 | 8 |
|
|
|
|
|
P.002 | Decel Time 1 | 20 |
|
|
|
|
|
P.003 | Minimum Speed | 0.5 |
|
|
|
|
|
P.004 | Maximum Speed | ||
|
|
|
|
P.005 | Current Limit | 110 |
|
|
|
|
|
P.0091 | Terminal Strip Analog Input Offset |
| |
P.0101 | Terminal Strip Analog Input Gain | 0.99 (50LR4060, 64LR4060) | |
|
| 1.030 (41LR4060) | |
P.011 | Terminal Strip Analog Input Configure | 4 |
|
|
|
|
|
P.013 | Output Relay Configuration | 2 |
|
|
|
|
|
P.027 | Forward/Reverse Configuration | 1 |
|
|
|
|
|
P.028 | Speed Display Scaling | ||
|
|
|
|
P.043 | Fault Auto Reset Attempts | 10 |
|
|
|
|
|
P.044 | Fault Auto Reset Time | 30 |
|
|
|
|
|
P.052 | AUTO/MAN Key Disable | ON | |
|
|
|
|
H.000 | Motor Nameplate Volts | ||
H.001 | Motor Nameplate Base Frequency | ||
|
|
| |
H.002 | Motor Nameplate Amps | 1.03 x Motor Nameplate Amps | |
|
|
| |
H.021 | AC Line Volts | ||
|
|
| |
H.022 | Overfrequency Limit | ||
|
|
|
|
r.001 | Analog Output 1 Source | 4 |
|
r.0021 | Analog Output 1 Offset | 60 (50LR4060, 64LR4060) | |
|
| 135 (41LR4060) | |
r.0031 | Analog Output 1 Gain | 0.505 (50LR4060, 64LR4060) | |
|
| 0.503 (41LR4060) | |
r.035 | Relay Output 1 (NO) Configuration | 5 |
|
|
|
|
|
r.036 | Relay Output 2 (NO/NC) Configuration | 2 |
|
|
|
|
|
r.037 | Relay Output 3 (NO/NC) Configuration | 1 |
|
|
|
|
|
r.046 | Relay Output 3 Delay Time |
| |
|
|
|
|
r.050 | Speed Detection Level 1 | 35 |
|
|
|
|
|
1These parameters must be tuned or calibrated per the VFD Control Verification procedures (running and
For
Identifying Parameter Defaults For Carrier Drives |