Carrier D2-3466-2 instruction manual Identifying Alarm Codes and Recovering

Page 25

6.4.1 Identifying Alarm Codes and Recovering

Drive alarm codes are shown in table 6.2. Note that the alarm code will only be displayed for as long as the problem exists. Once the problem has been corrected, the alarm code will disappear from the display.

Table 6.2 – List of Alarm Codes

 

Alarm

 

 

Code

Description

Alarm Cause

Corrective Action

HIdc

High DC bus

The DC bus is charged above the

Increase the deceleration time in

 

voltage

trip threshold. (If U.018 > 415,

P.002, P.018.

 

 

DC bus is above 741 VDC. If U.018

 

 

 

415, DC bus is above 669 VDC.)

Install optional snubber resistor

 

 

 

braking kit.

 

 

 

Verify that the AC input is within

 

 

 

specification. Install an isolation

 

 

 

transformer if required.

 

 

 

Check the actual line voltage against

 

 

 

U.018.

I-Ac

V/Hz identification

V/Hz identification procedure is

Allow identification procedure to

 

procedure active

enabled and in progress.

finish.

 

 

 

Press keypad STOP/RESET to

 

 

 

cancel identification procedure if

 

 

 

desired.

I-En

V/Hz identification

H.020 = On; V/Hz identification

Proceed with V/Hz identification

 

procedure

procedure has been enabled but not

procedure, start drive and allow

 

enabled

started.

procedure to begin. Display will

 

 

 

change to I-Ac when drive is started.

 

 

 

Change H.020 to OFF to cancel

 

 

 

identification and clear I-En if

 

 

 

desired.

LIL

Low AC input line

AC input line is low.

Adjust line voltage parameter (H.021

 

 

For SVC, indicates DC bus is being

or U.018) to match actual AC line

 

 

regulated. No corrective action is

voltage.

 

 

required.

 

S-Ac

Vector self-tuning

Vector self-tuning is enabled and in

Allow vector self-tuning procedure to

 

active

progress.

finish.

 

 

 

Press keypad STOP/RESET to

 

 

 

cancel vector self-tuning procedure

 

 

 

if desired.

S-En

Vector self-tuning

U.008 = On; vector self-tuning has

Proceed with vector self-tuning, start

 

enabled

been enabled but not started.

drive and allow self-tuning

 

 

 

procedure to begin. Display will

 

 

 

change to S-Ac when drive is

 

 

 

started.

 

 

 

Change U.008 to OFF to cancel

 

 

 

self-tuning and clear S-En if desired.

Troubleshooting the Drive

6-7

Image 25
Contents Carrier VFD Quick Reference Page Page Page Page Page Contents Carrier VFD Quick Reference Getting Assistance from Reliance Electric Required PublicationsCarrier VFD Quick Reference Replace with 2.fm 11 X 17 Z-fold Carrier VFD Quick Reference Monitor Mode Carrier VFD Quick Reference For Carrier Drives Carrier VFD Quick Reference Record the following nameplate information Record the following job informationCarrier VFD Quick Reference Verifying That DC Bus Capacitors Are Discharged Test Equipment Needed To TroubleshootPOS NEG TP1 TP2 Initial DC Bus Checking the Power Modules and Motor with Input Power Off Igbt Alarm Codes Troubleshooting the Drive Using Error CodesFault Codes Error LogAlarm Code Description Alarm Cause Corrective Action Identifying Alarm Codes and RecoveringFault Code Description Fault Cause Corrective Action Identifying Fault Codes and RecoveringIPL OPL Asymmetrical Bus When Input Ground Fault ExcessiveSlow Ramp Rate of DC Bus DC Carrier VFD Quick Reference Troubleshooting the Drive Code Fault Description Fault Cause Corrective Action Identifying Fatal Fault Codes and RecoveringResetting a Checksum CHS Fault Indentifying PMC Board Fault Codes and RecoveringStatus of LEDs Fault Description Corrective Action Model Amps Code Number Technical Writing Internal Use DIFPage Page Publication D2-3466-2 May 2005 -- Supercedes D2-3466-1 June