To Install the Heat Shield:
1.Determine if the heat shield is required. Do so by mea- suring the vertical distance between the top horizontal surface of the elbow to any combustible surface above. If the distance is more than 4 inches, the heat shield is NOT required. If it is 4 inches or less, the heat shield IS REQUIRED. Install per the following steps. See Figure 19.
Figure 19. | COMBUSTIBLE |
| SURFACE |
| 3” MIN. |
| (76 mm) |
| HEAT |
| SHIELD |
2.Fasten the shield in place using the pilot holes provided in the part. The shield should be oriented such that the 13 1/8 inch dimension (longest dimension) is running in the same direction the elbow is pointing. The shield should be centered directly above the elbow, and positioned so that it creates a 1/2 inch airspace between the shield and the combustible surface. See Figure 20.
CORRECT | INCORRECT |
| COMBUSTIBLE SURFACE |
| DIRECTION |
| UP |
| HEAT SHIELD |
| 90° ELBOW |
Figure 20. |
|
•If the combustible materials are not in place at the time of install the elbow heat shield may be screwed to the exhaust pipe (see Figure 21). Cut the tabs as shown and bend down. Secure the heat shield to the pipe maintain- ing 3” to 4” between the pipe and shield.
SCREW |
3 in. |
(76mm) |
Figure 21. |
Refer to Cinch Pipe and Termination Cap installation in- structions.
•Continue adding vent components, locking each suc- ceeding component into place.
•Ensure that each succeeding vent component is securely fitted and locked into the preceding component in the vent system.
•90° elbows may be installed and rotated to any point around the preceding component’s vertical axis. If an elbow does not end up in a locked position with the preceding component, attach with a minimum of two (2) sheet metal screws.
4. Install Support Brackets
Refer to Cinch Pipe and Termination Cap installation in- structions.
Figure 22. Adding Venting Components
22 |