Quadra-Fire QV36DC-A owner manual VENTING WITH ONE 1 90 ELBOW, Venting with One 90 Elbow

Models: QV36DC-A

1 36
Download 36 pages 62.39 Kb
Page 14
Image 14
VENTING WITH ONE (1) 90° ELBOW

VENTING WITH ONE (1) 90° ELBOW

V

 

H

1’ MIN. (305mm)

2’

MAX. (610mm)

2’ MIN. (610mm)

4’

MAX. (1.22m)

3’ MIN. (914mm)

6’

MAX. (1.86m)

4’ MIN. (1.22m)

8’

MAX. (2.4m)

V+H=40’ MAX. (12.4m)

H = 8’ MAX. (2.4m)

NOTE: On vertical venting configurations where the vertical component is over 10 feet install the vertical baffle included in the manual bag assembly to improve flame appearance.

V

H

Figure 11. Venting with One 90° Elbow

VENTING WITH ONE (1) 90° ELBOW

V (FT.)

H (FT.)

 

1’ MIN. (305mm)

5’ MAX.

(1.52m)

2’ MIN. (610mm)

10’ MAX.

(3.1m)

3’ MIN. (914mm)

15’ MAX.

(4.65m)

4’ MIN. (1.22m)

20’ MAX. (6.2m)

 

V+H= 40’ MAX. (12.4MM) H = 20’ MAX. (6.2m)

H

V

H

V

NOTE: If a 90o elbow is first attached to the unit, the maximum horizontal run is 3-feet (914mm).

NOTE: For corner installations: A 6-inch (152mm) section of straight pipe may need to be attached to the fireplace before a 90o elbow, to allow the vent pipe to clear the top standoffs.

Figure 12. Venting with One 90° Elbow

Quadra-FireQV36DC-A2161-900 Rev. C • 6/09