Quadra-Fire QV36DC-A Flue Restrictor Instructions, Straight Up, Adjustable Flue, Restrictors

Models: QV36DC-A

1 36
Download 36 pages 62.39 Kb
Page 12
Image 12
STRAIGHT UP

STRAIGHT UP

CAP

 

VERTICAL VENTING

V (FT.)

40’ MAX. (12.4 M)

NOTE: On vertical vent-

V

ing configurations over

 

20 feet install the flue re-

 

strictor (2027-102). See

 

flue restrictor installation

 

instructions.

 

Figure 6.

Straight Up Vertical Venting

Flue Restrictor Instructions

1.Remove screws with a 1/4 nut driver. Adjust to desired position per table. See Flue Restricting chart.

 

ADJUSTABLE FLUE

Figure 7.

RESTRICTORS (2)

- CHART -

Vertical

Top Vent

Top Vent

Rear Vent

Rear Vent

 

NG

LP

NG

LP

4’

2-2

2-3

No

No

 

 

 

Restrictor

Restrictor

8’

3-3

2-3

2-2

No

 

 

 

 

Restrictor

15’

3-4

3-4

3-3

2-3

20’

4-4

3-4

3-4

3-4

25’

4-4

3-4

3-4

3-4

30’

4-4

4-4

4-4

3-4

35’

4-4

4-4

4-4

3-4

40’

4-5

4-4

4-4

4-4

Adjustable Flue Restrictor (see Figure 8).

5

4

3

2

1

1

2

3

4

5

Figure 8

Quadra-FireQV36DC-A2161-900 Rev. C • 6/09

15

Page 12
Image 12
Quadra-Fire QV36DC-A Flue Restrictor Instructions, Straight Up, VERTICAL VENTING V FT 40’ MAX. 12.4 M, Adjustable Flue