Qualstar 501440 Rev. G operation manual Configuring the Fibre Channel Loop ID

Page 59

6.7Configuring the Fibre Channel Loop ID

The Id Mode must be configured for either “Soft” or “Fixed” addressing. Using “Soft” addressing, the Fibre Channel Option connects to an arbitrated loop using the first available AL_PA, scanning from the highest valid address to the lowest. Using “Fixed” addressing, the user selects a specific arbitrated loop address (AL_PA) to connect with. If the selected address is not available, the Fibre Channel Option will connect with the first available address it finds. The use of “Soft” or “Fixed” addressing is based on the user’s installation requirements.

Soft addressing can be configured when address conflicts are not likely. If the Fibre Channel Option is connected directly to the computer’s HBA (Host Bus Adapter), the selection of a specific Loop Id is not usually required. For example, Emulex HBA driv- ers scan for an available address starting from the low Fibre Channel address range. The FCO begins scanning for an available address starting from the high Fibre Chan- nel address range. This avoids address conflicts and the FCO Loop Id will be assigned the same value each time it is restarted.

Hard addressing should be configured if address conflicts can occur. This can happen if the FCO is connected to a Fibre Channel Hub. Since many HBA drivers map the Fi- bre Channel Loop Id to a SCSI Bus/Target address, this mandates that the Fibre Channel Loop Id be very stable, and cannot be allowed to change if the system is sim- ply restarted. This might happen if soft addressing were used and the Fibre Channel Option found its previous address taken. Selecting a fixed address is a way to prevent the FCO Loop Id from changing if the system is restarted.

If the computer’s HBA uses the World Wide Port Name (WWPN) convention instead of the Loop Id to map to a SCSI Bus/Target/Lun address, the value of the Loop Id is no longer important. The WWPN is always unique and consistent under all conditions. In the future, all addressing will likely use the WWPN.

C••••••Fibre•Channel

•Device

SOFT

Id Mode 0:

Loop Id 0:

nnn

Topology 0:

LOOP

Single Bay or one side of a Dual Bay Library

C••••••Fibre•Channel

•Device Left

•Device Right

L Id Mode 0: SOFT

L Loop Id 0: nnn

L Topology 0: LOOP

R Id Mode 0: SOFT

R Loop Id 0: nnn

R Topology 0: LOOP

Dual Bay Library with two FCO’s

The Configuration\Fibre Channel menu panel displays the SCSI device in- terface and configures the Fibre Channel Interface to host. The menu sets the Fibre Channel Option host topology. The “Topology” has two selections, LOOP and FABRIC. The LOOP selection configures the Fibre Channel Option for Arbitrated Loop (FC-AL) operation. The FABRIC selection configures the Fibre Channel Option for Switch Fab- ric (FC_SW) operation. If the mode is LOOP, the Id Mode and Loop Id entries are available.

501440 Rev. G

FCO Type C Installation

6-19

Image 59
Contents 501440 Rev. G Fibre Channel OptionCopyright 2004 by Qualstar Corporation All Rights Reserved Important Manual/Firmware Revision InformationQualstar Corporation Table of Contents Maintenance Menu Maintenance\Fibre Channel\ Log Left or Right Status Screen Subject Document Who Should Read This ManualIntroduction QualstarGefahr Important Safety InformationUnpacking UnpackingFC Interface Link General DescriptionProduct Description Models Type B Fibre Channel Option Product Description Drive Cabling for TLS-5/6/8000 and 58/68/88xxx Libraries Fibre Channel Option FCO Type a Installation ConsiderationsTLS-62xx and 82xx Drive Cabling Diagram Installation Installing a Fibre Channel OptionService Panel Rear View of TLS FCO Type a Installation Executive Pcba Identification Model CH0 Cable CH1 Cable CH2 Cable 10 Channel Connections Initializing the Fibre Channel Option 11 End View of D Connector on Gbic AdapterQualstarTLS-4000 FC Please Wait Status message Status ConditionDual Bay Library with two FCO’s Configuring the Fibre Channel Loop IDConfiguring the Fibre Channel Scsi Devices Interface Rescan FCO Type B Interconnect Cabling Fibre Channel Option FCO Type B Installation ConsiderationsFCO Type B Installation Component Description Cabling for TLS-412xxx Libraries Connectors on Rear of FCO Connectors on Rear of TLS-412xxxConnector Locations on the Rear of the TLS-412xxx Cabling for TLS-58xxx, 68xxx and 88xxx Libraries TLS-412xxx Cabling DiagramTLS-58xxx, 68xxx Connectors on RearRight Side TLS-58xxx/68xxx/88xxx Cabling Diagram Example of Cables Secured to the Rear of the TLS Securing the Cables to the TLSQualstarTLS-412180 FC Please Wait CFibreChannel Device Id Mode Configuring the Fibre Channel Scsi Devices Interface FCO Type B Installation FCO Type C Interconnect Cabling Fibre Channel Option FCO Type C Installation ConsiderationsFCO Type C Installation Bottom View of the Type C Fibre Channel Bridge/Router FCO Components Located on Bottom of FCO Cabling for TLS-4000, TLS-46xxx and TLS-412xxx Libraries Connectors on Rear of TLS-42xxConnectors on Rear of TLS-44xx Preferred TLS-46xxx Fibre Channel Option Cable Connections Preferred TLS-412xxx Fibre Channel Option Cable Connections Cabling for TLS-5/6/8000 and 58/68/88xxx Libraries Connectors on RearTLS-54xx, 64xx and TLS-84xx TLS-58xxx, 68xxx and TLS-88xxx Installing a Fibre Channel Option 10 Rear View of TLS 11 Fibre Channel Option in the Open Position Serial 13 Executive Pcba Identification 14 Detail of Connections Executive IV Pcba Shown 16 End View of Small Form Factor Pluggable Transceiver Status message Status Condition Configuring the Fibre Channel Loop ID FCO Type C Installation Configuring the Fibre Channel Scsi Devices Interface Rescan Configuration Menu Configuration MenuFrom Figure Location digit ExplanationConfiguration\Advanced Configuration MenuFibre Channel Left Configuration\Advanced\Changer\Mechanics MenuFibre Channel Fibre Channel Right Configuration\Advanced\Fibre Channel Left or Right MenuAlarm Router LUN 2 Ch0 / Ch1 FC Speed Fibre Channel Type B and C3 Ch0..Ch5 Scsi ID Fibre Channel Type B and C 4 Ch0..Ch5 Scsi Speed Fibre Channel Type B and CTime Hour Date DayDate Month Date YearLoop Id Left or Right Configuration\Fibre Channel MenuId Mode Left or Right Topology 0 / Topology 1 Left or Right Loop Id Rescan Configuration\Fibre Channel\Device Left or Right MenuManuf Scsi ChannelScsi ID Scsi LunMaintenance Menu Maintenance MenuPrivate menu access Maintenance Menu Base Lvl Maintenance\Fibre Channel MenuMaintenance\Fibre Channel\Info Left or Right Status Screen Backplane IdDaughtr Bd Id Board RevCpld Rev Memory MBCPU Temp Type a and B FCOs only Maintenance\Fibre Channel\ Log Left or Right Status ScreenUpdate Air TempLog Status Screen Sample Event text description Event Code Program Label Repacking Repacking the Fibre Channel OptionPreparation for Packing Remove the Gbic or SFP Adapter from the Fibre Channel Option Channel Connections in Type a FCO Detail of Auxpwr and Serial Connections in a Type a FCO Detail of Connections in a Type C FCO Screw Locations in an FCO Type a Shown Packing the Fibre Channel Option