EMC Installation Instructions

To ensure electromagnetic compatibility (EMC), the following installation instructions should be completed. These steps help to reduce interference. Consider the following:

Grounding of all system elements to a central ground point

Shielding of all cables and signal wires

Filtering of power lines

A proper enclosure should have the following characteristics:

A)All metal conducting parts of the enclosure must be electrically connected to the back plane. These connections should be made with a grounding strap from each element to a central grounding point . 

B)Keep the power wiring (motor and power cable) and control wiring separated. If these wires must cross, be sure they cross at 90 degrees to minimize noise due to induction.

C)The shield connections of the signal and power cables should be connected to the screen rails or clamps. The screen rails or clamps should be conductive clamps fastened to the cabinet. 

D)The cable to the regeneration resistor must be shielded. The shield must be connected to ground at both ends.

E)The location of the AC mains filter has to be situated close to the drive so the AC power wires are as short as possible.

F)Wires inside the enclosure should be placed as close as possible to conducting metal, cabinet walls and plates. It is advised to terminate unused wires to chassis ground. 

G)To reduce ground current, use at least a 10mm2 (6 AWG) solid wire for ground connections.

Grounding in general describes all metal parts which can be connected to a protective conductor, e.g. housing of cabinet, motor housing, etc. to a central ground point. This central ground point is then connected to the main plant (or building) ground.

Or run as twisted pair at minimum.

Cable Screens Grounding

Cable (Twisted Pair Conductors)

Conductive Clamp – Must contact bare cable shield

and be secured to metal backplane.

MN1851

CE Guidelines 8-3

Image 62
Contents Lin+Drive Servo Control Table of Contents Ii Table of Contents MN1851 Minimum system requirementsAppendix B 24VDC Logic Power InputAppendix a Iv Table of Contents MN1851 CE Compliance Limited WarrantySection General Information Could result in damage to property Product Notice Intended useCould result in injury or death General Information MN1851Do not apply AC power before you ensure that grounds are Do not touch any circuit board, power device or electricalConnection before you first ensure that power has been Voltages that are conducted to its power input terminals.General Information MN1851 Section Product Overview Control Outputs Encoder OutputSection Receiving and Installation Mechanical InstallationGND Receiving & Installation MN1851Control Recommended System Grounding 1 phase for UL Recommended System Grounding 1 phase for CEInput Power Conditioning System Grounding Ungrounded Distribution SystemBreaker Wire Size for units without Power SupplyX1 Power Connections Mm2Baldor Control Components not provided with ControlBaldor Baldor Option S Option P Control Regen Resistor EarthBreaker Baldor Option P Control Important LPxAxxxx-xxx3 onlyTo use an M4 bolt 12mm in length Holes in the top and bottomEnclosure are for cable clamps. Be sure Longer bolts may short circuit11 Motor Connections for UL 12 Motor Connections for CE13 Optional M-Contactor Connections Single Ended Connection Differential Connection Control Input WiringX3 Control Inputs & Digital I/O Connections X3 Digital Inputs Opto Isolated Inputs uses CrefOpto Input Signal Conditions Signal Name Opto Input Signal DefinitionProcess Duration Time Required DurationX3 Digital Outputs Opto Output Signal ConditionsFault Relay MaO1Control TXD X6 RS232 / 485 ConnectionsNull Modem Cable Connections ComputerRS485 What is a termination resistor?Where are these resistors placed? How many resistors should my system have?TX+ RX+ Dgnd = Twisted PairTX+ Dgnd GND TX+ RX+ Dgnd GNDX7 Encoder Output Buffered Encoder Output at X7 ConnectorX7 Pin Signal Name ReservedX9 Encoder and Hall Feedback LPxAxxxx-Exxx Control Address Setting Section Switch Setting and Start-UpSwitch AS1 Settings Address Setting, AS1-1 to AS1-4 for Multi-Drop ApplicationsOffset Tuning Setting of switches AS1-5 to AS1-8Switch Function AS1-5 to AS1-8 DescriptionPower On Checks Start-Up ProcedurePower Off Checks ProcedureSwitch Setting & Start-Up MN1851 Section Operation Installing Software on your PCHost Communications Setup Windows Windows NTUsing The Setup Wizard Flowchart of the Setup Wizard Operation MN1851Page There are 7 parts to the setup procedure Motor Motor parameters. Click Download when finishedEncoder Feedback Encoder FeedbackEncoder Feedback Motor pitch mm 60.96 Lmcf All Micron Counts / meter Counts / mmOperating Mode Selection Screen Operating ModeCurrent Parameter MN1851 OperationSoftware Triggered MAI4 MAI3 MAI2 MAI1Index channel, Capture and Actual Position Procedure to define home positionHome Set this value. Click Download when finished DriftFile SetupMain Menu Choice Descriptions EditFunctions TuningWatch MotionPLC Program Menu HelpMeters/second Velocity Parameters RPM m/sLinear Motor MN1851 Troubleshooting Section Troubleshooting1Operating Mode Indications OverviewLong as the error is less than ± 215 ± Section Specifications & Product Data Identification+0 to 40. Above 40 C, derate the continuous and peak SpecificationsTo 3300 feet 1000 meters. Derate the continuous Output current by 2.5% per C above 40 C. MaximumPeak output current by 1.1% for each 330 feet Description UnitSpecifications & Product Data MN1851 24VDC Logic Power Input Option LPxAxxxx-xxx3 only24VDC Logic Power Input Option LP4Axxxx-xxx3 only Velocity ControlEncoder Input Feedback RegenerationClearance Requirements all sizes 0.06″ 15mm top and bottom DimensionsSize A, B and C CE Declaration of Conformity Wiring of Shielded Screened CablesSection CE Guidelines EMC Conformity and CE MarkingGrounding Earth EMC Wiring TechniqueCE Guidelines MN1851 EMC Installation Instructions Cable Screens GroundingEncoder Input Cable Grounding Input Signal Cable GroundingSimulated Encoder Output Cable Grounding To ControllerMating Connector by connector number for spare parts Section Accessories and OptionsConnectors CablesDepth = F AC Filter DimensionsAccessories & Options MN1851 Fo rRegeneration Resistor PackageAccessories & Options MN1851 General Tuning Rules Appendix a Manual TuningTools are available to make tuning easier, such as Manual TuningManual Tuning MN1851 There are 7 parts to the setup procedureParameters. Click Download when finished Motor15240 000,000 10,000,000 Figure A-13 Current Parameter Screen Figure A-14 Velocity Parameter Screen Drift Figure A-15 Drift Parameter ScreenFigure A-16 Select Manual Tuning Figure A-17 Inertia and Load Response Examples Tracking factorFigure A-18 PI Compensation Menu Page Graphic Screen Plotting of MoveControl Window Jog BlockSyntax General structure of the Ascii command Appendix B Command SetLin Ascii Command Set General MN1851 Command Set B-1Encoder Pulses/rev ResolutionParameters and Units Input Buffer Overflow command line exceeded 80 char Start-up with Terminal Communication and Command ExamplesExecution Error invalid command Control Design Failure invalid control designBasic System Parameters Motor Parameters MTR. prefixed General Settings System ConstantsCommand Set MN1851 Drive Parameters typical DRV. prefixedMN1851 Command Set B-5 Software Limit Switches ParametersVariables None Software Limit Switches Methods Command Description Units Range Default E2 / Par. setPLC.LINE PLC ParametersVariables None PLC Methods RelayDigital Interface Parameters MN1851 Command Set B-7OCI Interface Parameters Analog Interface ParametersSystem Variables General Variables Queries / modifications of Fault Listing VariablesX1 Possible Faults X1 Fault Display Description Methods Communication Settings ParameterMN1851 Command Set B-9 VariableData Record REC. prefixed Variable Queries of System Variables, Status, Faults Single ValuesData Record REC. prefixed Parameters Eeprom related Operation Mode Control Normal Modes ParametersMemory related methods Queries / modifications RAM related Normal Modes VariablesCurrent mode Methods Sys.mod Current mode ParametersCurrent mode Variables Query for actual current commandVelocity mode Methods Sys.mod 1 & Sys.mod Velocity mode ParametersVelocity mode Variables MN1851 Command Set B-13JOG.TYPE Jog ParametersJOG.TIME JOG.VELVariables MN1851 Command Set B-15Position Controller Position Controller Parameters HW.PLC HW.GRFXHW.GRSH HW.RESBaldor Electric Company  Baldor Electric Company MN1851 10/00 C&JLin+Drive Servo Control MN1851