MGE UPS Systems 100 installation manual Comet S31 7.5/10KVA, Connections

Page 24

2. Installation

2.8 Installation of the PowerServices TelPac external unit for Comet UPSs

For this installation it is necessary to de-energise the UPS. The various PowerServices TelPac components do not present an electrocution hazard for the installer.

It is necessary to initially check:

That the UPS is equipped with a JBUS/RS485 communication card 16 in one of its slots situated at the back or that such a card is available for installation (ref. 6761294 JOJO).

That a UPS-secured outlet is available near to the UPS (L < 1m) as well as a telephone outlet (L < 4m).

Comet S31 7.5/10KVA

< 1m

Page 24 - 34003602EN/AB

Installation (UPS de-energised)

16Clean the place where it is planned to fit the external unit using

the solvent cleaning kit (see figures).

Remove the protective adhesive under the external unit.

Place the external unit as shown, according to the type of UPS. Press down hard for 10 seconds to fix the adhesive. Configure the JBUS / RS485 card as shown in section 2.6 and place it in the recommended location.

 

Connections

 

Connect one end of the power supply adapter cord to the back of

< 4m

the external unit (5V DC) and the other end to a UPS-secured

 

outlet near to the UPS.

 

Connect the external unit to the JBUS / RS485 communication

 

card 16 using the supplied cable: wire T- on terminal T-, wire R+

 

on terminal R+, then the shielding.

 

Connect one end of the telephone cable to the "phone" port on

 

the external unit and the other end to the telephone outlet. If the

 

wall outlet is not compatible with the connector on the cable, use

 

an adapter.

Fix the cables to the back of the UPS using the attached adhesive cable holders.

Image 24 Contents
PowerServicesTM TelPac Installation manual2 34003602EN/AB Special precautions IntroductionEnvironment Recycling of packagingForeword EMC compatibilityFederal Communication Commission FCC statement Radio and Telecommunications compatibilityModem compatibility and supported countries List of countries supported by the modemPictogram symbols Contents Maintenance Unpacking and checking the contents PresentationOverview Country Teleservice Centre FunctionsTechnical data sheet Power supplyRS485 Port ModemIndicator lights Status Green UPS indicator Card version External versionStatus Red CD indicator Card version External version Installation ProcedurePreliminary check Various installation types Recommendations Fitting the warning labelMGE Attention Onduleur sous Teleservice Galaxy PWSetting up the RS485 link Single-unit type installationGeneral UPS with JbusImpedance matching and bias settings Configuring the shielding terminal = ShieldingConfiguring the RS485 card for Comet For CometConfiguring the Rauz card for Galaxy Installing the PowerServices TelPac card ConnectionComet S31 7.5/10KVA ConnectionsComet S31 15/20KVA Open the doors giving access to Galaxy view with doors open and protective panels in place Connecting contact type inputs PowerServices TelPac card 2 inputsPowerServices TelPac external unit 2 inputs + 4 extensions 5V BMaintenance Cable diagramsComet link cable ref