American Power Conversion SUDP4000I, SUDP8000I, SUDP6000I External Connections, Mains Connections

Page 10

External Connections

Notes:

As a standard, the Smart-UPS DP is made for single-phase connection.

Due to the leakage current of 3.5 to 10 mA, the Smart-UPS DP must always be grounded according to local regulations.

Mains Connections

Make these connections only if no optional equipment (see the Optional Equipment Installation, page 8) is being used.

Mains Fuses and Cable Dimensions

Standard System

System

Mains Fuse * (Fm)

Input Cable UPS

Output Cable UPS

4kV

25A

3x6 mm²

3x4 mm²

6kV

40A

3x10 mm²

3x10 mm²

8kV

50A

3x16 mm²

3x10 mm²

10kV

63A

3x16 mm²

3x16 mm²

* Din gl Types

MAINS

Fm

L

N

PE

INPUT CABLE UPS

OUTPUT CABLE UPS

LOAD L

N

L

N

L

N

+

UPS

COM

EPO

PORT

 

990-1007A, Revision 2 9/99

4

Image 10
Contents Smart-UPS DP Uninterruptible Power Supply Models 990-1007A, Revision 2 9/99 About Your New UPS Page Table of Contents 990-1007A, Revision 2 9/99 Electrical Safety SafetyHandling Safety Replacement and Recycling of BatteriesInspection Initial InspectionUnpacking Switching Off Installation InstructionsPlacement Checking Electrical DataExternal Connections Mains ConnectionsRear Views RED BlackData Common FaultPrincipal Diagram common fault Computer Interface Port OptionalJ100 EPO Relay PC Board J100Galvanic Isolation Transformer Optional Equipment InstallationGalvanic Isolation Transformer Connections UPS External Service Bypass Panel SBP Service Bypass Panel ConnectionsSBP and Galvanic Isolation Transformer Connections External Run Battery Cabinet Detail of Smart-UPS DP with an Extended Run Battery CabinetSetting the Voltage Switching OnSwitching Off External Service Bypass Panel OperationLED Display LEDsBatteries ServiceStorage Limited Warranty SpecificationsSUDP10000I Regulatory Agency Approvals Latin America, South America APC Contact InformationInternet Europe, Middle East, Africa