Common Fault

The function of the common fault relay is factory preset. For changing the factory setting, please contact your local dealer.

Principal Diagram (common fault)

1

2

3

4

NC

NO

Com

Com

Data:

Relay contacts - ohmic load

DC min./max.: 12VDC 20mA/60VDC 1A

AC min./max.: 12VAC 20mA/250VAC 8A

Computer Interface Port (Optional)

PowerChute® power management software and interface kits can be used with this UPS. If used, connect the interface cable to the 9-pin computer interface port on the back panel of the UPS. Secure the connector’s screws to complete the connection.

Note:

The serial cable should not be connected to the UPS until the user is ready to install the software.

Emergency Power Off (EPO) Remote Shut Down and Signal Relay Port (Optional)

The EPO function uses the Remote Shut Down (RSD) pins on the X005 25-pin Sub-D female connector on the back of the UPS. The J100 PC board with the mate (a 25 pin Sub D male) to the X005 and a screw capture connector for each of the pins list below is included the UPS.

UPS on

Pin 2 -15 short circuit

Pin 2 -14 open circuit

UPS off

Pin 2 -14 short circuit

Pin 2 -15 open circuit

Bypass mode

Pin 4 -17 short circuit

Pin 4 -16 open circuit

Normal operation

Pin 4 -16 short circuit

Pin 4 -17 open circuit

Battery operation

Pin 6 -19 short circuit

Pin 6 -18 open circuit

Normal operation

Pin 6 -18 short circuit

Pin 6 -19 open circuit

Battery voltage low

Pin 8 -21 short circuit

Pin 8 -20 open circuit

Battery voltage normal

Pin 8 -20 short circuit

Pin 8 -21 open circuit

Galvanic isolated DC supply

 

 

5V / 30 mA or 12V / 20 mA

Pin 12 = PSU +

Pin 24 = PSU GND

Pull up resistor 2400ohm

Pin 11 = Pull up +

 

Remote shut down input

 

 

High: 3.5V to 25V

Pin 13 = RSD +

Pin 25 = RSD -

Low: -25V to 0.5V

 

 

Min. Pulse length: 1 sec

 

 

990-1007A, Revision 2 9/99

6

Image 12
Contents Smart-UPS DP Uninterruptible Power Supply Models 990-1007A, Revision 2 9/99 About Your New UPS Page Table of Contents 990-1007A, Revision 2 9/99 Safety Handling SafetyElectrical Safety Replacement and Recycling of BatteriesInitial Inspection InspectionUnpacking Installation Instructions PlacementSwitching Off Checking Electrical DataExternal Connections Mains ConnectionsRear Views RED BlackCommon Fault Principal Diagram common faultData Computer Interface Port OptionalJ100 EPO Relay PC Board J100Optional Equipment Installation Galvanic Isolation TransformerGalvanic Isolation Transformer Connections UPS External Service Bypass Panel SBP Service Bypass Panel ConnectionsSBP and Galvanic Isolation Transformer Connections External Run Battery Cabinet Detail of Smart-UPS DP with an Extended Run Battery CabinetSwitching On Switching OffSetting the Voltage External Service Bypass Panel OperationLED Display LEDsService BatteriesStorage Specifications Limited WarrantySUDP10000I Regulatory Agency Approvals APC Contact Information InternetLatin America, South America Europe, Middle East, Africa