Common Fault
The function of the common fault relay is factory preset. For changing the factory setting, please contact your local dealer.
Principal Diagram (common fault)
1 | 2 | 3 | 4 |
NC | NO | Com | Com |
Data:
Relay contacts - ohmic load
DC min./max.: 12VDC 20mA/60VDC 1A
AC min./max.: 12VAC 20mA/250VAC 8A
Computer Interface Port (Optional)
PowerChute® power management software and interface kits can be used with this UPS. If used, connect the interface cable to the
Note:
The serial cable should not be connected to the UPS until the user is ready to install the software.
Emergency Power Off (EPO) Remote Shut Down and Signal Relay Port (Optional)
The EPO function uses the Remote Shut Down (RSD) pins on the X005
UPS on | Pin 2 | Pin 2 |
UPS off | Pin 2 | Pin 2 |
Bypass mode | Pin 4 | Pin 4 |
Normal operation | Pin 4 | Pin 4 |
Battery operation | Pin 6 | Pin 6 |
Normal operation | Pin 6 | Pin 6 |
Battery voltage low | Pin 8 | Pin 8 |
Battery voltage normal | Pin 8 | Pin 8 |
Galvanic isolated DC supply |
|
|
5V / 30 mA or 12V / 20 mA | Pin 12 = PSU + | Pin 24 = PSU GND |
Pull up resistor 2400ohm | Pin 11 = Pull up + |
|
Remote shut down input |
|
|
High: 3.5V to 25V | Pin 13 = RSD + | Pin 25 = RSD - |
Low: |
|
|
Min. Pulse length: 1 sec |
|
|
| 6 |