American Power Conversion SUDP4000I, SUDP8000I Specifications, Limited Warranty, SUDP10000I

Page 22

Specifications

 

SUDP4000I

SUDP6000I

 

SUDP8000I

 

SUDP10000I

Acceptable input voltage

 

 

 

220/230/240V

 

 

 

 

+10%/-15% normal operation

 

 

 

±10% bypass operation

 

Input voltage (on-line operation)

 

220/230/240

VAC

 

230 volt output range

 

220/230/240 VAC

 

Nominal input frequency

 

 

50 or 60 Hz

 

Input protection

 

Resettable circuit breaker

 

Frequency limits (on-line operation)

 

50 or 60 Hz,

8%

 

 

Bypass Transfer time

 

2 ms typical, 5 ms maximum

 

Maximum load, Total

4000 VA

6000 VA

 

8000 VA

 

10000 VA

On-battery output voltage

 

 

 

230 VAC

 

On-battery frequency

 

50 or 60 Hz,

0.1 Hz;

 

 

 

unless synchronized to utility during brownout.

 

On-battery waveshape

 

Low-distortion sine wave

 

Overload protection (on-battery)

Overcurrent and short-circuit protected, latching shutdown on overload

Overload protection (on-line)

25A

40A

 

 

50A

 

63A

Noise filter

 

Normal and common

mode EMI/RFI suppression,

 

 

100 kHz to 10 MHz

 

Battery type

 

Spill proof, maintenance free, sealed lead-acid

 

Typical battery life

 

5 years, depending on number of discharge cycles

 

 

and ambient temperature

 

Typical recharge time

 

24 hours from total discharge

 

Operating temperature

 

0 to 40￿C (+32 to +104￿F)

 

Storage temperature

 

-15 to +45￿C (+5 to +113￿F)

 

Operating and storage relative humidity

 

30% to 95%, not condensing

 

Operating elevation

 

0 to +3,000 m (0 to +10,000 ft.)

 

Storage elevation

 

0 to +15,000 m (0 to +50,000 ft.)

 

Electromagnetic Compatibility (EMC)

 

 

EN50091-2

 

Electromagnetic Interference (EMI)

 

EN55022 Class A

 

Electromagnetic Immunity

 

IEC 801-2, 801-3, 801-4, 801-5, 1000-2-2

 

 

 

EN60555-1, -2, -3, EN61000-4-1, EN61000-4-11

Audible noise in dBA at 1 m (3 ft.)

 

 

45 dBA

 

 

 

Safety approvals

 

GS licensed by VDE to EN50091-1-1 and EN60950

Size (W x H x D)

 

315 x 650 x 610 mm

 

Weight

128 kg

 

 

 

138 kg

 

Limited Warranty

American Power Conversion (APC) warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase. Its obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products. To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from customer support (see the Service section of the User’s Manual). Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase. This warranty does not apply to equipment which has been damaged by accident, negligence, or misapplication or has been altered or modified in any way. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase.

EXCEPT AS PROVIDED HEREIN, AMERICAN POWER CONVERSION MAKES NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Some states do not permit limitation or exclusion of implied warranties; therefore, the aforesaid limitation(s) or exclusion(s) may not apply to the purchaser.

EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL APC BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, APC is not liable for any costs, such as lost profits or revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, costs of substitutes, claims by third parties, or otherwise.

990-1007A, Revision 2 9/99

16

Image 22
Contents Smart-UPS DP Uninterruptible Power Supply Models 990-1007A, Revision 2 9/99 About Your New UPS Page Table of Contents 990-1007A, Revision 2 9/99 Electrical Safety SafetyHandling Safety Replacement and Recycling of BatteriesInspection Initial InspectionUnpacking Switching Off Installation InstructionsPlacement Checking Electrical DataExternal Connections Mains ConnectionsRear Views RED BlackData Common FaultPrincipal Diagram common fault Computer Interface Port OptionalJ100 EPO Relay PC Board J100Galvanic Isolation Transformer Optional Equipment InstallationGalvanic Isolation Transformer Connections UPS External Service Bypass Panel SBP Service Bypass Panel ConnectionsSBP and Galvanic Isolation Transformer Connections External Run Battery Cabinet Detail of Smart-UPS DP with an Extended Run Battery CabinetSetting the Voltage Switching OnSwitching Off External Service Bypass Panel OperationLED Display LEDsBatteries ServiceStorage Limited Warranty SpecificationsSUDP10000I Regulatory Agency Approvals Latin America, South America APC Contact InformationInternet Europe, Middle East, Africa