External Service Bypass Panel (SBP)
Note:
The
manufactured by APC are used, the UPS system may be damaged and the warranty given by APC is repealed.
During the installation of the service bypass panel, you must attach a ferrite bead on the signal cable to ensure regulatory
compliance. A ferrite bead and its installation instructions are included in the literature kit.
The external service bypass panel isolates the system so that service can be carried out safely without any interruption to the load.
WARNING:
Be careful when operating the external service bypass panel. Follow the operating procedure described below carefully.
All pluggable cables between the
SBP is in the Bypass position.
When the SBP is switched from “Normal” to “Bypass” the
Service Bypass Panel
S y s te m In p u t | UP S S E RV ICE BYPAS S | S y s te m O u tp u t | |
| S BP100E |
|
|
| R e fe r to U s e r G u id e |
|
|
| fo r o p e r a tio n in s tru c tio n s |
| |
Q 0 0 1 |
| H 0 0 2 | Q 0 0 2 |
|
| ||
|
|
| N o rm a l B y pa s s |
| O nly op e rat e Q 00 2 | S0 0 2 |
|
| w he n H0 0 2 is O N |
|
P re s s a nd hold S 0 0 2 t o re que s t op e rat ion o f Q 0 0 2
| ! | T h i s p a n e l h a s t w o |
|
U P S In p u t | s o u r c e s o f p o w!e r . | U P S O u tp u t |
SBP Mounting Holes
B
C
X001
SYSTEM
INPUTX004
SYSTEM
OUTPUT
A
X010
X002
UPS INPUT X003
UPS OUTPUT
Key
SUDP001 SUDP002
A = 240 mm | 270 mm | |
B = | 240 mm | 330 mm |
C = | 4 x ø 6.5 mm |
Service Bypass Panel Connections
Standard system with Service Bypass Panel (SBP)
System | Mains Fuse*(Fm) | Input Cable SBP | Input Cable UPS |
4kV | 25A | 3x6 mm² | 3x6 mm² |
6kV | 40A | 3x10 mm² | 3x10 mm² |
8kV | 50A | 3x16 mm² | 3x16 mm² |
10kV | 63A | 3x16 mm² | 3x16 mm² |
*Din gl Types |
|
|
|
System | Output Cable UPS | Output Fuse SBP (Fo) | Output Cable SBP |
4kV | 3x4 mm² | 20A | 3x4 mm² |
6kV | 3x10 mm² | 32A | 3x10 mm² |
8kV | 3x10 mm² | 40A | 3x10 mm² |
10kV | 3x16 mm² | 50A | 3x16 mm² |