American Power Conversion SUDP8000I, SUDP6000I, SUDP4000I External Service Bypass Panel SBP

Page 16

External Service Bypass Panel (SBP)

Note:

The Smart-UPS DP must only be connected by service bypass panels (SBPs) manufactured by APC. If SBPs other than those

manufactured by APC are used, the UPS system may be damaged and the warranty given by APC is repealed.

During the installation of the service bypass panel, you must attach a ferrite bead on the signal cable to ensure regulatory

compliance. A ferrite bead and its installation instructions are included in the literature kit.

The external service bypass panel isolates the system so that service can be carried out safely without any interruption to the load.

WARNING:

Be careful when operating the external service bypass panel. Follow the operating procedure described below carefully.

All pluggable cables between the Smart-UPS DP and the SBP should be disconnected or should only be connected while the

SBP is in the Bypass position.

When the SBP is switched from “Normal” to “Bypass” the Smart-UPS DP no longer regulates and filters the input voltage.

Service Bypass Panel

S y s te m In p u t

UP S S E RV ICE BYPAS S

S y s te m O u tp u t

 

S BP100E

 

 

 

R e fe r to U s e r G u id e

 

 

 

fo r o p e r a tio n in s tru c tio n s

 

Q 0 0 1

 

H 0 0 2

Q 0 0 2

 

 

 

 

 

N o rm a l B y pa s s

 

O nly op e rat e Q 00 2

S0 0 2

 

 

w he n H0 0 2 is O N

 

P re s s a nd hold S 0 0 2 t o re que s t op e rat ion o f Q 0 0 2

 

!

T h i s p a n e l h a s t w o

 

U P S In p u t

s o u r c e s o f p o w!e r .

U P S O u tp u t

SBP Mounting Holes

B

C

X001

SYSTEM

INPUTX004

SYSTEM

OUTPUT

A

X010

X002

UPS INPUT X003

UPS OUTPUT

Key

SUDP001 SUDP002

A = 240 mm

270 mm

B =

240 mm

330 mm

C =

4 x ø 6.5 mm

Service Bypass Panel Connections

Standard system with Service Bypass Panel (SBP)

System

Mains Fuse*(Fm)

Input Cable SBP

Input Cable UPS

4kV

25A

3x6 mm²

3x6 mm²

6kV

40A

3x10 mm²

3x10 mm²

8kV

50A

3x16 mm²

3x16 mm²

10kV

63A

3x16 mm²

3x16 mm²

*Din gl Types

 

 

 

System

Output Cable UPS

Output Fuse SBP (Fo)

Output Cable SBP

4kV

3x4 mm²

20A

3x4 mm²

6kV

3x10 mm²

32A

3x10 mm²

8kV

3x10 mm²

40A

3x10 mm²

10kV

3x16 mm²

50A

3x16 mm²

990-1007A, Revision 2 9/99

10

Image 16
Contents Smart-UPS DP Uninterruptible Power Supply Models 990-1007A, Revision 2 9/99 About Your New UPS Page Table of Contents 990-1007A, Revision 2 9/99 Safety Handling SafetyElectrical Safety Replacement and Recycling of BatteriesInspection Initial InspectionUnpacking Installation Instructions PlacementSwitching Off Checking Electrical DataExternal Connections Mains ConnectionsRear Views RED BlackCommon Fault Principal Diagram common faultData Computer Interface Port OptionalJ100 EPO Relay PC Board J100Galvanic Isolation Transformer Optional Equipment InstallationGalvanic Isolation Transformer Connections UPS External Service Bypass Panel SBP Service Bypass Panel ConnectionsSBP and Galvanic Isolation Transformer Connections External Run Battery Cabinet Detail of Smart-UPS DP with an Extended Run Battery CabinetSwitching On Switching OffSetting the Voltage External Service Bypass Panel OperationLED Display LEDsBatteries ServiceStorage Limited Warranty SpecificationsSUDP10000I Regulatory Agency Approvals APC Contact Information InternetLatin America, South America Europe, Middle East, Africa