American Power Conversion SUDP4000I, SUDP8000I, SUDP6000I Optional Equipment Installation

Page 14

Optional Equipment Installation

Galvanic Isolation Transformer

The galvanic isolation transformer can be delivered for one- or two-phase connection. When connecting a Smart-UPS DP and galvanic isolation transformer, the AC bus and the wires for the thermo switch must be mounted. Please follow the instructions below.

Note:

If the cables in the galvanic isolation transformer have 4 wires, the wire marked no. 3 must be cut off.

Galvanic Isolation Transformer Connections

The AC bus from the galvanic isolation transformer must be mounted.

Note:

If the galvanic isolation module is installed it must be secured so that the neutral is grounded according to local regulations.

This is done in the galvanic isolation transformer with a wire between terminal 5 (PE) and 9 (neutral).

This wire is already mounted from the factory. If the Smart-UPS DP has to be grounded to a separate EDP earth, this is done

to terminal 9, after having removed the wire between terminals 5 and 9.

Standard System With Isolating Transformer (230 V)

System

Mains Fuse*

Input Cable

Input Cable UPS

Output Cable UPS

 

(Fm)

Transformer

 

 

4kV

25A

3x6 mm²

3x6 mm²

3x4 mm²

6kV

40A

3x10 mm²

3x10 mm²

3x10 mm²

8kV

50A

3x16 mm²

3x16 mm²

3x10 mm²

10kV

63A

3x16 mm²

3x16 mm²

3x16 mm²

*Din gl Types

MAINS

Fm

L

N

PE

Input L

Cable Tr.

N

Iso.Tr

L

N INPUT CABLE UPS OUTPUT CABLE UPS

.

L

N

L

N

UPS

Tr. Sw. cable

LOAD L

N

COM

EPO

PORT

 

990-1007A, Revision 2 9/99

8

Image 14
Contents Smart-UPS DP Uninterruptible Power Supply Models 990-1007A, Revision 2 9/99 About Your New UPS Page Table of Contents 990-1007A, Revision 2 9/99 Electrical Safety SafetyHandling Safety Replacement and Recycling of BatteriesUnpacking Initial InspectionInspection Switching Off Installation InstructionsPlacement Checking Electrical DataExternal Connections Mains ConnectionsRear Views RED BlackData Common FaultPrincipal Diagram common fault Computer Interface Port OptionalJ100 EPO Relay PC Board J100Galvanic Isolation Transformer Connections Optional Equipment InstallationGalvanic Isolation Transformer UPS External Service Bypass Panel SBP Service Bypass Panel ConnectionsSBP and Galvanic Isolation Transformer Connections External Run Battery Cabinet Detail of Smart-UPS DP with an Extended Run Battery CabinetSetting the Voltage Switching OnSwitching Off External Service Bypass Panel OperationLED Display LEDsStorage ServiceBatteries SUDP10000I SpecificationsLimited Warranty Regulatory Agency Approvals Latin America, South America APC Contact InformationInternet Europe, Middle East, Africa