American Power Conversion SUDP4000I, SUDP8000I, SUDP6000I, SUDP10000I External Run Battery Cabinet

Page 18

Standard System With Isolating Transformer (400 V) And SBP

System

Mains Fuse*

Input Cable

Input Cable UPS

Output Cable

 

(Fm)

Transformer

 

UPS

4kV

16A

3x2.5mm²

3x6mm²

3x6 mm²

6kV

25A

3x6 mm²

3x16 mm²

3x10 mm²

8kV

32A

3x10 mm²

3x16 mm²

3x10 mm²

10kV

40A

3x10 mm²

3x16 mm²

3x16 mm²

*Din gl Types

System

Output Cable UPS

Output Fuse SBP (Fo)

Output Cable SBP

4kV

3x4 mm²

20A

3x4 mm²

6kV

3x10 mm²

32A

3x10 mm²

8kV

3x10 mm²

40A

3x10 mm²

10kV

3x16 mm²

50A

3x16 mm²

MAINSLOAD

L1

L2

Fm

Fm

Input L1

Cable Tr.

L2

Iso.Tr

.

L

N

INPUT

L

SBP

CABLE

 

SBP

N

L

N

OUTPUT CABLE SBP

Fo L

N

PE

Tr. Sw. cable

X010

 

 

 

 

1 2

3

4

 

 

 

SBP

 

 

Input

Output

CABLE

 

 

 

cable

 

 

 

cable

 

UPS

 

 

 

UPS

 

 

 

 

 

 

 

 

L

N

L

N

1 2

3

4

 

 

 

MBS CONTROL

 

 

 

UPS

External Run Battery Cabinet

Note:

You must attach a ferrite bead to the signal cable of the extended run battery cabinet to ensure regulatory compliance. A ferrite

bead and its installation instructions are included in the literature kit.

For longer uninterrupted power during UPS on-battery operation, connect an extended run battery cabinet to the Smart-UPS DP. All connection diagrams show the UPS with an extended run battery cabinet already connected.

Detail of Smart-UPS DP with an Extended Run Battery Cabinet

L

N

L

N

 

UPS

 

UPS

MBS control

 

output Ext.

input

 

 

 

DC

 

 

 

UPS

 

 

 

Ext. Tr.

 

 

 

Th.

 

 

Ext.

Sw.

 

 

 

 

Batt

 

 

 

 

 

 

Temp.

+

DC

cable

Temp. sensor cable

+

DC

384V

Belt

Temp. sensor

990-1007A, Revision 2 9/99

12

Image 18
Contents Smart-UPS DP Uninterruptible Power Supply Models 990-1007A, Revision 2 9/99 About Your New UPS Page Table of Contents 990-1007A, Revision 2 9/99 Electrical Safety SafetyHandling Safety Replacement and Recycling of BatteriesInitial Inspection InspectionUnpacking Switching Off Installation InstructionsPlacement Checking Electrical DataExternal Connections Mains ConnectionsRear Views RED BlackData Common FaultPrincipal Diagram common fault Computer Interface Port OptionalJ100 EPO Relay PC Board J100Optional Equipment Installation Galvanic Isolation TransformerGalvanic Isolation Transformer Connections UPS External Service Bypass Panel SBP Service Bypass Panel ConnectionsSBP and Galvanic Isolation Transformer Connections External Run Battery Cabinet Detail of Smart-UPS DP with an Extended Run Battery CabinetSetting the Voltage Switching OnSwitching Off External Service Bypass Panel OperationLED Display LEDsService BatteriesStorage Specifications Limited WarrantySUDP10000I Regulatory Agency Approvals Latin America, South America APC Contact InformationInternet Europe, Middle East, Africa