American Power Conversion SUDP10000I Operating Instructions, Switching On, Switching Off

Page 19

Operating Instructions

Switching On

Switch on the mains fuse on the rear of the UPS. The Smart-UPS DP will perform a self-check ending with the LED display showing red/yellow/green, meaning that the unit is functioning properly. The unit performs a self-test automatically when turned on, and every two weeks thereafter.

Switch the 1/0 switch on the front of the Smart-UPS to 1 (up). The acoustic alarm will give a short beep when output power is available.

Note:

Whenever the UPS is turned on and utility voltage is present, the charger maintains battery charge.

Switching Off

Switching off the Smart-UPS DP must be done in the following way:

Switch the on/off switch on the front to 0 (down).

Switch off (down) the mains fuse on the rear.

Switch off the main supply.

Setting the Voltage

If the AC power mains voltage is not 230 V (the factory-set default for the UPS), use the PowerChute® power management software to set it to the correct voltage. This must be done with no load connected to the UPS.

External Service Bypass Panel Operation

The external service bypass panel (SBP) isolates the Smart-UPS DP so service can be carried out safely without any interruption to the load.

WARNING:

The Smart-UPS DP must only be connected by service bypass panels (SBPs) manufactured by APC. If SBPs other than those

manufactured by APC are used, the UPS system may be damaged and the warranty given by APC is repealed.

When the SBP is switched from “Normal” to “Bypass” the output voltage is no longer adjusted or controlled by the

Smart-UPS DP.

Before operating the SBP, check that the Smart-UPS DP is running in normal operation. When S002 is pushed, H002 must go

on within 1 second - if not, release S002 immediately- bypass mains is outside tolerances and the SBP cannot be operated.

Q001:

0 :

Supply voltage to Smart-UPS DP is OFF.

 

I :

Supply voltage to Smart-UPS DP is ON.

Q002:

Normal :

The Smart-UPS DP is running in normal operation.

 

 

The electrical load is supplied directly from the Smart-

 

 

UPS DP.

 

Bypass:

The electrical load is supplied via the bypass switch

 

 

from the mains.

Note:

Ensure that the UPS is operating on-line (Normal mode) before switching to the Bypass mode.

How to Switch From Normal to Bypass Mode

1.Press and hold the S002 switch and, within one (1) second turn the Q002 switch to the Bypass position.

2.Turn the Q001 switch to the “0” position. The UPS can now be shut down or serviced.

How to Return to Normal Mode

1.Turn the Q001 switch to the “I” position.

2.Turn the Smart-UPS DP on by switching the front panel switch from the “0” to the “I” position.

3.Push and hold the S002 switch and, within one (1) second turn the Q002 switch to the Normal position.

13

990-1007A, Revision 2 9/99

Image 19
Contents Smart-UPS DP Uninterruptible Power Supply Models 990-1007A, Revision 2 9/99 About Your New UPS Page Table of Contents 990-1007A, Revision 2 9/99 Replacement and Recycling of Batteries SafetyHandling Safety Electrical SafetyInspection Initial InspectionUnpacking Checking Electrical Data Installation InstructionsPlacement Switching OffMains Connections External ConnectionsRED Black Rear ViewsComputer Interface Port Optional Common FaultPrincipal Diagram common fault DataJ100 J100 EPO Relay PC BoardGalvanic Isolation Transformer Optional Equipment InstallationGalvanic Isolation Transformer Connections UPS Service Bypass Panel Connections External Service Bypass Panel SBPSBP and Galvanic Isolation Transformer Connections Detail of Smart-UPS DP with an Extended Run Battery Cabinet External Run Battery CabinetExternal Service Bypass Panel Operation Switching OnSwitching Off Setting the VoltageLEDs LED DisplayBatteries ServiceStorage Limited Warranty SpecificationsSUDP10000I Regulatory Agency Approvals Europe, Middle East, Africa APC Contact InformationInternet Latin America, South America