Operating Instructions
Switching On
Switch on the mains fuse on the rear of the UPS. The
Switch the 1/0 switch on the front of the
Note:
Whenever the UPS is turned on and utility voltage is present, the charger maintains battery charge.
Switching Off
Switching off the
•Switch the on/off switch on the front to 0 (down).
•Switch off (down) the mains fuse on the rear.
•Switch off the main supply.
Setting the Voltage
If the AC power mains voltage is not 230 V (the
External Service Bypass Panel Operation
The external service bypass panel (SBP) isolates the
WARNING:
The
manufactured by APC are used, the UPS system may be damaged and the warranty given by APC is repealed.
When the SBP is switched from “Normal” to “Bypass” the output voltage is no longer adjusted or controlled by the
Before operating the SBP, check that the
on within 1 second - if not, release S002 immediately- bypass mains is outside tolerances and the SBP cannot be operated.
Q001: | 0 : | Supply voltage to |
| I : | Supply voltage to |
Q002: | Normal : | The |
|
| The electrical load is supplied directly from the Smart- |
|
| UPS DP. |
| Bypass: | The electrical load is supplied via the bypass switch |
|
| from the mains. |
Note:
Ensure that the UPS is operating
How to Switch From Normal to Bypass Mode
1.Press and hold the S002 switch and, within one (1) second turn the Q002 switch to the Bypass position.
2.Turn the Q001 switch to the “0” position. The UPS can now be shut down or serviced.
How to Return to Normal Mode
1.Turn the Q001 switch to the “I” position.
2.Turn the
3.Push and hold the S002 switch and, within one (1) second turn the Q002 switch to the Normal position.
13 |