American Power Conversion SURT15000, 20000 VA user manual Wiring Specifications

Page 12

Wiring Specifications

Adhere to national and local electrical codes when wiring.

 

Input Connections

 

 

Output Connections

 

Main Input

 

 

Hardwire

 

 

Single-Phase: Wire to L1, N, and

 

Single-Phase: Wire to L1, N, and

 

Three-Phase: Wire to L1, L2, L3, N, and

Three-Phase: Wire to L1, L2, L3, N, and

 

Bypass Input (optional)

 

Single-phase PDU

 

 

Single-Phase: Wire to B1, N, and

 

XL battery pack PDU to UPS: Wire L1, N,

 

 

 

 

 

Three-Phase: Wire to B1, B2, B3, N, and

 

 

 

 

System

Wiring

Number

Voltage

Current

External Input

Wire Size

 

 

of Phases

 

Full Load

Circuit Breaker

(typical)*

 

 

 

 

(maximum)

(typical)

 

SURT15000UXI/

Input

1

220/230/

83 A

100 A / 1-pole

25/35 mm2

UXICH

 

 

240 Vac

 

 

(2/1 AWG)

 

Input

3

380/400/

28 A / phase

35 A / 3-pole

6 mm2

 

 

 

415 Vac

 

 

(8 AWG)

 

Output

1

220/230/

65 A

not required

25 mm2

 

 

 

240 Vac

 

 

(2 AWG)

 

Output

3

380/400/

22 A / phase

not required

6 mm2

 

 

 

415 Vac

 

 

(8 AWG)

SURT20000XI/

Input

1

220/230/

105 A

125 A / 1-pole

35/50 mm2

UXICH

 

 

240 Vac

 

 

(1/0 AWG)

 

Input

3

380/400/

35 A / phase

50 A / 3-pole

10 mm2

 

 

 

415 Vac

 

 

(6 AWG)

 

Output

1

220/230/

87 A

not required

35 mm2

 

 

 

240 Vac

 

 

(1 AWG)

 

Output

3

380/400/

29 A / phase

not required

10 mm2

 

 

 

415 Vac

 

 

(6 AWG)

*Terminal screw tightening torque: 40 lbf-in (4.5 N-m) The acceptable input frequency range is 40 to 70 Hz.

The output frequency is user selectable. Refer to the PowerView display menu screens for available options.

8

Smart-UPS RT 15000/20000 VA 230 Vac UXI/UXICH Tower User Manual

Image 12
Contents UXI/UXICH Page Contents Page Unpack package contents About this UPSSpecifications Environmental SpecificationsInstallation Install PowerViewConnect PowerView Route ethernet cable and install top cover and bezelsFront panel access routing ethernet cable under top cover Accessories Optional accessoriesInstall input and output wiring trays in UPS rear panel Wiring Specifications Adhere to national and local electrical codes when wiringInput wiring options Input/Output Jumper ConfigurationsSingle phase input, single phase output, single feed Single phase input, single phase output, dual feedThree phase input, single phase output, single feed Three phase input, three phase output, single feedThree phase input, single phase output, dual feed Three phase input, three phase output, dual feedOutput wiring options L3 L2 L1 OSJBattery Safety APC battery solutionQualified electrician should perform the installation Servicing of external batteriesThird party battery solution Each battery system must have identical Amp-hrsPowerView Interface Display Battery operationOperation Normal operationNavigating menu screens Main Menu ScreenMenu Tree Navigating sub menu screensSub menu screens SystemView Log Connect power to UPS and load Connect load to UPSCommunication Ports Emergency Power Off EPO EPO ConnectorInput/Output Jumper Configurations Page Refer to Contact Information in this Option 2 Correct bypass input Service and Transport Warranty claims Regulatory Agency Approvals Models