American Power Conversion SURT15000, 20000 VA user manual Third party battery solution

Page 18

Third party battery solution

Batteries must be Sealed Lead-Acid type. Use 50 A, 250 Vdc fuses with an Interrupt rating of >20,000 A.

Ensure that the external batteries are wired prior to connecting the batteries to the UPS.

Two separate, isolated 192 V battery systems are required when using a third party battery solution. One cable assembly must be wired to each 192 V battery system. Two cable assemblies are included with the UPS, one for each 192 V battery system.

Each battery system must have identical Amp-hrs.

Connect the ground and wire the battery system

1.Connect the ground wires (supplied), to each battery enclosure ground and the ground screw on the back of the UPS.

2.Cut off one of the connectors on each cable assembly exposing the positive and negative wires in each cable.

3.Connect the positive and negative wires to the positive and negative terminals on each external battery system. Ensure that the proper polarities are connected.

4.Plug the cable connectors into the battery connector receptacles on the back of the UPS.

5.Enter the external battery capacity through the PowerView menu.

a.This setting determines battery runtime and battery charge rate.

b.The number entered in the menu screen Ext Bat Cap, must equal the number of Amp-hrs in one of the identical battery systems.

Fuse

Battery System

192 V 192 V

grnd

Battery System

192 V 192 V

grnd

14

Smart-UPS RT 15000/20000 VA 230 Vac UXI/UXICH Tower User Manual

Image 18
Contents UXI/UXICH Page Contents Page Unpack package contents About this UPSSpecifications Environmental SpecificationsInstallation Install PowerViewConnect PowerView Route ethernet cable and install top cover and bezelsFront panel access routing ethernet cable under top cover Accessories Optional accessoriesInstall input and output wiring trays in UPS rear panel Wiring Specifications Adhere to national and local electrical codes when wiringInput wiring options Input/Output Jumper ConfigurationsSingle phase input, single phase output, single feed Single phase input, single phase output, dual feedThree phase input, single phase output, dual feed Three phase input, single phase output, single feedThree phase input, three phase output, single feed Three phase input, three phase output, dual feedOutput wiring options L3 L2 L1 OSJQualified electrician should perform the installation Battery SafetyAPC battery solution Servicing of external batteriesThird party battery solution Each battery system must have identical Amp-hrsOperation PowerView Interface DisplayBattery operation Normal operationNavigating menu screens Main Menu ScreenMenu Tree Navigating sub menu screensSub menu screens SystemView Log Connect power to UPS and load Connect load to UPSCommunication Ports Emergency Power Off EPO EPO ConnectorInput/Output Jumper Configurations Page Refer to Contact Information in this Option 2 Correct bypass input Service and Transport Warranty claims Regulatory Agency Approvals Models