Emergency Power Off (EPO)

The output power can be disabled in an emergency by closing a switch connected to the EPO.

Adhere to national and local electrical codes when wiring.

The switch should be connected in a normally open switch contact. External voltage is not required; the switch is driven by 12 V internal supply. In closed condition, 2 mA of current are drawn.

The EPO switch is internally powered by the UPS for use with non-powered switch circuit breakers.

The EPO circuit is considered a Class 2 circuit, (UL, CSA standards) and an SELV circuit (IEC standard).

EPO PORT

(located on rear panel)

EPO Connector

Strip the insulation from one end of each wire to be used for connecting the EPO.

Insert a screwdriver into the slot above the terminal to be wired. Insert the stripped end of the wire into the terminal.

Remove the screwdriver to secure the wire in the terminal. Repeat for each terminal.

Both Class 2 and SELV circuits must be isolated from all primary circuitry. Do not connect any circuit to the EPO terminal block unless it can be confirmed that the circuit is Class 2 or SELV. If circuit standard cannot be confirmed, use a contact closure switch.

Use one of the following cable types to connect the UPS to the EPO switch.

CL2: Class 2 cable for general use.

CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.

CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft.

CLEX: Limited use cable for use in dwellings and for use in raceways.

For installation in Canada: Use only CSA certified, type ELC, (extra-low voltage control cable).

For installation in other countries: Use standard low-voltage cable in accordance with national and local regulations.

Smart-UPS RT 15000/20000 VA 230 Vac UXI/UXICH Tower User Manual

21

Image 25
Contents UXI/UXICH Page Contents Page About this UPS Unpack package contentsEnvironmental Specifications SpecificationsInstall PowerView InstallationRoute ethernet cable and install top cover and bezels Connect PowerViewFront panel access routing ethernet cable under top cover Optional accessories AccessoriesInstall input and output wiring trays in UPS rear panel Adhere to national and local electrical codes when wiring Wiring SpecificationsInput/Output Jumper Configurations Input wiring optionsSingle phase input, single phase output, dual feed Single phase input, single phase output, single feedThree phase input, three phase output, single feed Three phase input, single phase output, single feedThree phase input, single phase output, dual feed Three phase input, three phase output, dual feedL3 L2 L1 OSJ Output wiring optionsAPC battery solution Battery SafetyQualified electrician should perform the installation Servicing of external batteriesEach battery system must have identical Amp-hrs Third party battery solutionBattery operation PowerView Interface DisplayOperation Normal operationMain Menu Screen Navigating menu screensNavigating sub menu screens Menu TreeSystem Sub menu screensView Log Connect load to UPS Connect power to UPS and loadCommunication Ports EPO Connector Emergency Power Off EPOInput/Output Jumper Configurations Page Refer to Contact Information in this Option 2 Correct bypass input Service and Transport Warranty claims Models Regulatory Agency Approvals