Condition | PowerView Display | Reason for Message | Corrective Action | |
Message | ||||
|
|
| ||
|
|
|
| |
General | # of batteries increased. | At least one battery pair has been | No corrective action is necessary. | |
Status |
| added to the system. |
| |
|
|
|
| |
| # of batteries decreased. | At least one battery pair has been |
| |
|
| removed from the system. |
| |
|
|
|
| |
| # External Battery Packs | At least one external battery pack has |
| |
| increased. | been connected to the UPS. |
| |
|
|
|
| |
| # External Battery Packs | At least one external battery pack has |
| |
| decreased. | been disconnected from the UPS. |
| |
|
|
|
| |
Module | Bad Battery Pair. | A battery pair has failed and requires | Refer to battery pair installation in | |
Failure |
| replacement. | the external battery pack user | |
|
|
| manual. | |
|
|
|
| |
Threshold | Load Power Is Above | The load has exceeded the user- | Option 1) Use the display interface to | |
Alarm | Alarm Limit. | specified load alarm threshold. | raise the alarm threshold. | |
|
|
| Option 2) Reduce the load | |
|
|
|
| |
| Load Is No Longer Above | The load exceeded the alarm | No corrective action is necessary. | |
| Alarm Threshold. | threshold. The situation has been |
| |
|
| corrected. Either because the load |
| |
|
| decreased or the threshold was |
| |
|
| increased. |
| |
|
|
|
| |
| Min Runtime Restored. | The system runtime dropped below |
| |
|
| the configured minimum and has been |
| |
|
| restored: |
| |
|
| 1) Additional battery modules were |
| |
|
| installed. |
| |
|
| 2) The existing battery modules were |
| |
|
| recharged. |
| |
|
| 3) The load was reduced. |
| |
|
| 4) The user- specified threshold was |
| |
|
| decreased. |
| |
|
|
|
|
23 |