Condition | PowerView Display | Reason for Message | Corrective Action | |
Message | ||||
|
|
| ||
|
|
|
| |
General | Shutdown Due To Low | The UPS shutdown while on battery | No corrective action is necessary. | |
Fault | Battery. | operation. | Note: Should this situation reoccur, | |
|
|
| consider increasing battery capacity. | |
|
|
|
| |
| Bypass Not Available Input | The frequency or voltage is out of | Correct the input voltage to | |
| Freq/Volt out Of Range. | acceptable range for bypass. This | acceptable frequency or voltage. | |
|
| message occurs when the UPS is |
| |
|
| online. |
| |
|
|
|
| |
| Mains Not Available. Input | The frequency or voltage is out of |
| |
| Frq/Volt Out of Range. | acceptable range for normal |
| |
|
| operation. |
| |
|
|
|
| |
| Emergency PSU Fault. | Redundant Emergency Power Supply | Contact APC Customer Support. | |
|
| Unit (PSU) is not working. Internal | Refer to Contact Information in this | |
|
| diagnostic fault. The UPS will | manual. | |
|
| continue to operate normally. |
| |
|
|
|
| |
| Fan Fault | A fan has failed. | Contact APC Customer Support. | |
|
|
| Refer to Contact Information in this | |
| Static Bypass Switch Fault. | The static bypass switch has failed. | manual. | |
|
|
|
| |
| System Failure Detected by | The system has detected an internal | Check for other alarms. | |
| Surveillance. | error. | If the problem persists contact APC | |
|
|
| Customer Support. Refer to Contact | |
|
|
| Information in this manual. | |
|
|
|
| |
| System Not Synchronized | System cannot synchronize to bypass | Option 1) Decrease input frequency | |
| to Bypass. | mode.Bypass mode may be | sensitivity. | |
|
| unavailable. | Contact APC Customer Support. | |
|
|
| Refer to Contact Information in this | |
|
|
| manual. | |
|
|
| Option 2) Correct bypass input | |
|
|
| voltage to provide acceptable | |
|
|
| frequency or voltage. | |
|
|
|
| |
| UPS In Bypass Due To | The UPS has transferred to bypass | Contact APC Customer Support. | |
| Fault. | mode due to a fault. | Refer to Contact Information in this | |
|
|
| manual. | |
|
|
|
| |
| UPS In Bypass Due To | The load has exceeded the power | Decrease the load. | |
| Overload. | capacity. |
| |
|
|
|
| |
| UPS Is Overloaded. | The load has exceeded the system | Option 1) Decrease the load. | |
|
| power capacity. | Option 2) Check the load distribution | |
|
|
| on the three phases through the | |
|
|
| PowerView display. If the load is | |
|
|
| unevenly distributed, adjust the load | |
|
|
| distribution. | |
|
|
|
|