APC 900XL, 2000XL, 600XL user manual Operation

Page 24

5.0 Operation

5.6 Option switches - continued

5.6.2 Option switch 2

Option switch 2 controls different functions depending upon the UPS version type.

120 Vac version

The UPS's factory set input voltage limits for on-line and SmartBoost operation are given in section 9.0 and are centered on the nominal input voltage of 120 Vac. When Option switch 2 is set to the on ( I ) position, the upper and lower transfer voltages are lowered by 4% and are centered on a nominal input of 115 Vac. This option is useful where the nominal input voltage is 110 to 115 Vac.

220/230/240 Vac version

The UPS's factory set on-battery output voltage and input voltage limits for on-line and SmartBoost operation are appropriate for use in regions where the nominal line voltage is 220 to 230 Vac. When Option switch 2 is set to the on ( I ) position, the upper and lower transfer voltages are raised by 4% and are centered on a nominal input of 240 Vac. In addition, the on-battery output voltage is increased to 240 Vac.

5.6.3 Option switch 3

When Option switch 3 is set to the on ( I) position, the UPS's audible alarm is disabled for the first 30 seconds of an extended utility fault. This function is useful where brief power interruptions are frequent and cause the alarm to become annoying.

5.6.4 Option switch 4

When Option switch 4 is set to the on ( I) position, the UPS's low battery warning interval before shutdown due to battery capacity exhaustion is extended. This function is useful where the UPS is protecting a computer system that requires a longer warning interval before power loss to perform a graceful shutdown.

Page 22

Image 24
Contents Smart-UPS Important safety instructions Radio Frequency InterferenceTable of contents Introduction OverviewBattery replacement indicators and test SmartBoostRemote interfaces Extended capabilitiesSafety EnglishSécurité Sicherheit Deutsch¡ Seguridad Presentation 600VA and 900VA models 120 Vac versionFront view Rear view 600VA and 900VA models 220/230/240 Vac version 2000VA model 120 Vac version 2000VA model 120 Vac version options Option2000VA model 220/230/240 Vac version Front viewInstallation PlacementInstall bracket 2000VA models, 220/230/240 Vac version Receiving inspectionConnect battery pack Connect UPS to service and enable Connect UPS to serviceEnable UPS Check Site Wiring Fault indicator 120 Vac versions Switch on load equipmentSwitch on the UPS Plug loads into UPSDisplay features OperationBattery capacity bar graph Output power bar graphAudible alarm On-battery operationLow battery Line voltage bar graphOption switches Replace batteryOption switch OverloadOperation Status reporting MonitoringPower management Operation customizingOperation PowerChute Software UPS MonitoringInterface Kits Computer interface port Difficulty Difficulté Schwierigkeit Dificultad Troubleshooting chart FheNbRc FeiiVNbR OMliR MOkVed ke kMaR Battery replacement check Obtaining Service Storing the UPS Storage conditionsExtended storage Specifications Transfer characteristicsOutput characteristics InputBattery and charger Noise and surge suppressionEnvironment PhysicalTypical recharge time and run time versus load 1 600VA, 900VA models2 2000VA models + 3.6 hrDeclaration of Conformity Limited Warranty Life support policy∗ Mailing