9.0 Specifications

9.4 Noise and surge suppression

Surge energy rating (one time, 10/1000 µs waveform): 480 J.

Surge current capability (one time, 8/20 µs waveform): 6500 Amp peak maximum.

Surge response time: 0 ns (instantaneous) normal mode, <5 ns common mode.

Surge voltage let-through:<0.3%, [<2%] of appliedANSI C62.41 CategoryA± 6 kV test waveform.

Noise filter: normal and common mode EMI/RFI suppression, 100 kHz to 10 MHz.

9.5 Battery and charger

Battery type: spill proof, maintenance free sealed lead-calcium.

Typical battery life: 3 to 6 years - depends on number of discharge cycles and ambient temperature.

Typical recharge time: see tables in section 9.9.

9.6 Environment

Operating temperature: 0°C to 40°C (32°F to 104°F).

Storage temperature: -15°C to 45°C (5°F to 113°F).

Operating and storage relative humidity: 0 to 95%, non-condensing.

Operating elevation: 0 to 3,000 m (10,000 ft).

Storage elevation: 0 to 15,000 m (50,000 ft).

Electromagnetic immunity: IEC 801-2, 801-3, 801-4, 801-5; severity levels III or IV.

Audible noise; 600VA, 900VA models: < 50 dBA at 1 m (3 ft).

Audible noise, 2000VA models < 60 dBA at 1 m (3 ft).

9.7 Physical

Size; 600VA, 900VAmodels: Electronics and Battery pack enclosures each 9.1"H x 6.9"W x 17.8"D (23.1 x 17.5 x 45.2 cm).

Size, 2000VA model: Electronics enclosures is 18.0"H x 6.9"W x 17.8"D (45.7 x 17.5 x 45.2 cm). The Battery pack is 9.1"H x 6.9"W x 17.8"D (23.1 x 17.5 x 45.2 cm).

Weight; 600VA, 900VA models: Electronics enclosure is 32 lbs (14.5 kg), shipping weight is 37 lbs (16.8 kg). The Battery pack is 62 lbs (28.1 kg), shipping weight is 67 lbs (30.4 kg). Weight, 2000VA model: Electronics enclosure is 61 lbs (27.7 kg), shipping weight is 68 lbs (30.8 kg). The Battery pack is 64 lbs (29.0 kg), shipping weight is 69 lbs (31.3 kg).

9.8 Approvals

Safety approvals: UL per 1778, CSA per C22.2, TUV per IEC 950.

EMC verification: FCC, DOC ClassA verified; EN55022 Class A verified.

Page 37

Image 39
Contents Smart-UPS Radio Frequency Interference Important safety instructionsTable of contents Overview IntroductionExtended capabilities Battery replacement indicators and testSmartBoost Remote interfacesEnglish SafetySécurité Deutsch Sicherheit¡ Seguridad Presentation 600VA and 900VA models 120 Vac versionFront view Rear view 600VA and 900VA models 220/230/240 Vac version 2000VA model 120 Vac version Option 2000VA model 120 Vac version optionsFront view 2000VA model 220/230/240 Vac versionReceiving inspection InstallationPlacement Install bracket 2000VA models, 220/230/240 Vac versionConnect battery pack Connect UPS to service Connect UPS to service and enableEnable UPS Plug loads into UPS Check Site Wiring Fault indicator 120 Vac versionsSwitch on load equipment Switch on the UPSOperation Display featuresOutput power bar graph Battery capacity bar graphLine voltage bar graph Audible alarmOn-battery operation Low batteryOverload Option switchesReplace battery Option switchOperation Monitoring Status reportingOperation customizing Power managementOperation PowerChute Software UPS MonitoringInterface Kits Computer interface port Difficulty Difficulté Schwierigkeit Dificultad Troubleshooting chart FheNbRc FeiiVNbR OMliR MOkVed ke kMaR Battery replacement check Obtaining Service Storing the UPS Storage conditionsExtended storage Input SpecificationsTransfer characteristics Output characteristicsPhysical Battery and chargerNoise and surge suppression Environment1 600VA, 900VA models Typical recharge time and run time versus load+ 3.6 hr 2 2000VA modelsDeclaration of Conformity Life support policy Limited Warranty∗ Mailing