6.0 UPS Monitoring

6.4 Computer interface port

The computer interface port is diagramed below for your reference. Those with technical abilities wishing to use this port in a special application should be aware of the following limitations and capabilities of the interface.

Outputs at pins 3, 5 and 6 are actually open collector outputs which must be pulled up to a common referenced supply no greater than +40 Vdc. The transistors are capable of a maximum non-inductive load of 25 mAdc. Use only Pin 4 as the common.

The output at Pin 2 will generate a LO to HI RS-232 level upon transfer of the output load to power derived from the UPS’s battery. The pin is normally at a LO RS-232 level.

The UPS will shut down when a HI RS-232 level, sustained for 4.5 s, is applied to Pin

1. The UPS responds to this signal, following a delay, only during mains failures (load is operating from the UPS’s internal power source).

An unregulated +24 Vdc appears at Pin 8 of the interface port whenever the UPS is powered. The supply is limited to 40 mAdc maximum.

Page 27

Image 29
Contents Smart-UPS Radio Frequency Interference Important safety instructionsTable of contents Overview IntroductionSmartBoost Battery replacement indicators and testRemote interfaces Extended capabilitiesEnglish SafetySécurité Deutsch Sicherheit¡ Seguridad Front view Rear view Presentation600VA and 900VA models 120 Vac version 600VA and 900VA models 220/230/240 Vac version 2000VA model 120 Vac version Option 2000VA model 120 Vac version optionsFront view 2000VA model 220/230/240 Vac versionPlacement InstallationInstall bracket 2000VA models, 220/230/240 Vac version Receiving inspectionConnect battery pack Connect UPS to service Connect UPS to service and enableEnable UPS Switch on load equipment Check Site Wiring Fault indicator 120 Vac versionsSwitch on the UPS Plug loads into UPSOperation Display featuresOutput power bar graph Battery capacity bar graphOn-battery operation Audible alarmLow battery Line voltage bar graphReplace battery Option switchesOption switch OverloadOperation Monitoring Status reportingOperation customizing Power managementOperation Interface Kits PowerChute SoftwareUPS Monitoring Computer interface port Difficulty Difficulté Schwierigkeit Dificultad Troubleshooting chart FheNbRc FeiiVNbR OMliR MOkVed ke kMaR Battery replacement check Obtaining Service Extended storage Storing the UPSStorage conditions Transfer characteristics SpecificationsOutput characteristics InputNoise and surge suppression Battery and chargerEnvironment Physical1 600VA, 900VA models Typical recharge time and run time versus load+ 3.6 hr 2 2000VA modelsDeclaration of Conformity Life support policy Limited Warranty∗ Mailing