1.0 Introduction
1.2 SmartBoost
SmartBoost allows continuous
1.3 Battery replacement indicators and test
The UPS provides both visual and audible Replace Battery indications. The indications are based on the result of an actual load test on the battery. By exercising the UPS’s battery during a startup test, the UPS is able to detect a weak battery before it is put into service. In applications where the UPS is not turned off daily, or where the UPS is purposely left operating unattended, the UPS automatically conducts this self test every 14 days.
1.4 Remote interfaces
The UPS provides a remote computer interface capable of full bidirectional
1.5 Extended capabilities
Via the UPS's remote interface, the user can access advanced monitoring, power manage- ment and operation customizing functions. Monitored parameters include line voltage, line frequency, output power, output voltage, battery capacity, battery voltage and internal temperature. Power management functions include scheduled shutdown, power failure simulation, and remote turn off. UPS functions that can be customized include the automatic self test and low battery warning intervals; shut down,