Agilent Technologies 6624A, 6621A, 6627A, 6622A, 6623A manual Connecting the Load

Page 44

A fixed overvoltage threshold of approximately 120% of the maximum rated output voltage is built into each output. Because the fixed overvoltage circuit is biased from the output terminals, it can be activated and provide protection even when the supply is not connected to the ac power line.

The OVRST command restores the programmed voltage and current values and clears the OV once the cause of the overvoltage has been eliminated.

OVERCURRENT--when the overcurrent protection feature is enabled, and the output is sourcing current and enters the +

CCoperating mode, the output will be disabled (set to zero volts and minimum current) and the word OVERCURRENT will appear on the front panel display. In addition the OC status bit is set for that output. The OCRST command restores the programmed voltage and current values and clears the OC once the cause of the overcurrent condition has been eliminated. Refer to Chapter V for programming details.

UNREGULATED OUTPUT--the supply informs the user when output regulation is not guaranteed. This can occur when attempting to sink excessive currents below 2.5 volts or when operating outputs in parallel. The UNR annunciator on the front panel and the UNR bit in the status register indicate that the specified output is unregulated. Line voltage dropout or an incorrectly set ac power module can also cause the output to become unregulated. If line voltage dropout continues, the supply shuts down and will return to the power-up condition when normal line voltage is restored.

OVERTEMPERATURE--shuts down the linear pass and downprogrammer of the output that has reached an unsafe operating temperature. Operation of the other outputs is unaffected. An overtemperature can occur because of excessively high ambient temperature, a blocked fan, or insufficient space at the sides for adequate air circulation. When an overtemperature condition occurs, the word OVERTEMP appears in the front panel display and the OT status bit is set. This circuit resets automatically and restores the output approximately 30 seconds after the temperature drops sufficiently for safe operation.

ERROR--if the power supply receives an invalid command either through the front panel or the GP-IB, the ERR annunciator on the front panel comes on and the ERR bit in the serial poll register is set. The power supply does not execute the command and remains at previously set values. Pushing the ERR button in local mode displays the error message and clears the error. The error indicator may also indicate that an instrument failure has occurred. Refer to Appendix D for further details.

CONNECTING THE LOAD

Each terminal block cover on the rear panel is secured by a locking tab which snaps into a slot at the left of the terminal block. To remove, insert a screwdriver into this rectangular slot and move the locking tab to the left. When the locking tab releases, gently pull the terminal block cover away from the terminal block. To reinstall the cover, align it over the terminal block and gently press it into position until the locking tab engages.

SHOCK HAZARD Turn off ac power before making rear panel connections. All wires and straps must be properly connected with terminal block screws securely tightened. Replace terminal block covers before reapplying power.

Each rear terminal block has six M3.5 x 0.6 x 6 mm screws for attaching wires (see Figure 2-2). Load connections to the supply are made at the + V and -V terminals on each terminal block Do. not connect unterminated wires to the load terminals. Wires used for load connections must be properly terminated with termination connectors securely attached. Remember to replace the impact resistant plastic covers (Agilent P/N 06624-20007) over the terminal blocks after making connections.

46 Output Connections and Operating Information

Image 44
Contents Operating Manual Agilent Part NoCertification Safety Summary Safety Summary Environmental ConditionsDeclaration of Conformity EMCWhat this Manual Contains Table Of Contents Remote Operation Local OperationCommand Summary Error MessagesCalibration Programming With a Series 200/300 ComputerSafety Considerations General InformationIntroduction Instrument and Manual IdentificationAccessories DescriptionModel Output Combinations AvailableBasic Operation GP-IB BoardOutput Boards Definitions SpecificationsQualifying Conditions Output Response Characteristics Specifications Source EffectSupplemental Characteristics Outputs Low High Voltage Temperature CoefficientReadback Resolution OVPLow Voltage General Information General Information General Information General Information Location and Cooling InstallationInitial Inspection Input Power Requirements Line FuseGP-IB Line FusesPower Cord Line Voltage ConversionGP-IB Interface Connector Turning On Your Supply Front Panel Controls and IndicatorsGetting Started 15V 35A Output Controls and Indicators Number Controls/lndicators Test Pattern of all Display Segments at Power-on Normal Self Test IndicationsChecking Out Your Supply Using Local Control Sample Self-Test Failure DisplayCurrent Test Voltage TestOvervoltage Test Introduction To Remote Operation Iset EnterOCP RSTSending a Remote Command OutputReading the GP-IB Address AddrDisp a Often Used CommandsGetting Data From The Supply Disp a Returning the Supply to Local Mode Output Connections and Operating Information Output RangesRange Selection Protection FeaturesOperating Quadrants Typical Output Range Characteristics Connecting the Load Page Wire Size Wire Bundled 10 a 20 a AWGRemote Voltage Sensing Multiple LoadsRemote Voltage Sensing Remote Sense ConnectionsOutput Type Formula Output Noise ConsiderationsProgramming Response Time with an Output Capacitor Open Sense LeadsOvervoltage Trigger Connections External Trigger CircuitEquivalent Internal OV Trigger Circuit Parallel Operation Power Supply Protection ConsiderationsBattery Charging Maximum Allowable Voltage Setting CV OperationCC Operation Remote SensingSeries Operation 13. Series Connections with Local Sensing CV OperationSpecifications for Series Operation 14. Series Connections with Remote SensingPage Interface Function Remote OperationGP-IB Operation GP-IB Address Selection Numeric Data Power-On Service Request PONProgramming Syntax Sheet 1 of 2. Syntax Forms for Power Supply Commands Sheet 2 of 2. Syntax Forms for Power Supply Commands Power Supply Commands Header Output Channel Data RangePower Supply Commands Initial ConditionsVoltage Programming VSET?VOUT? Current ProgrammingAvg Current-Avg RangeAvg Resolution IOUT?Range Switching Output On/OffOvercurrent Protection OCP Overvoltage OV ProtectionOVSET? Status Reporting Clear CommandMultiple Output Storage & Recall Functional Relationship of Status Registers UNR +CCUnmask 2,XXX ASTS?UNMASK? FAULT? Service Request GenerationBit Assignment of the Serial Poll Register PON RQS ERR RDY FAUSRQ? Reprogramming Delay RQS BitDisplay On/Off Other QueriesTEST? CMODE?GP-IB Code Error Messages Explanation Front Panel ResponseFront Panel Response CodeTEST? Responses Code ExplanationLocal Mode Local OperationLocal Control Of Output Functions GeneralSetting Voltage Setting CurrentSetting Overvoltage Protection Resetting Overvoltage ProtectionResetting Overcurrent Protection Displaying the Contents of the Fault RegisterSetting the Reprogramming Delay Setting the Supply’s GP-IB AddressLocal Control Of System Functions ConditionDisplaying Error Messages Addr EnterSTO Enter RCL EnterCalibration Procedures Test Equipment and Setup RequiredFigure A-1. Calibration Setup See Figure General Calibration ProcedureTable A-1. Calibrat ion Commands Header Channel Data Syntax Page Calibration Program 10 ! Calibration ExampleClear Voltmeter Output Buffer PauseFnend Input ANY More Outputs to CALIBRATE? Y or N,X$Disp END of Calibration Program Page Voltage and Current Programming Programming With a Series 200/300 ComputerPath Names Voltage and Current Programming With Variables Voltage and Current ReadbackProgramming Power Supply Registers Print OUTPUT1 is in CV Mode END ifService Request and Serial Poll Present StatusEnable Intr OFF IntrPrint ’’OVERVOLTAGE on Output #1 Print Overvoltage on Output #2Error Detection Programming Outputs Connected In Parallel Stored Operating StatesInput Enter Voltage LIMIT’’,V Input Enter Operating VOLTAGE,V1Programming Outputs Connected In Series Input Enter the Desired Current Limit POINT,ICommand Description Command SummaryTable C-1. Command Summary Table C-l. Command Summary PON? ROM?SRQ? Error Codes and Messages Power-On Self Test Messages Error ResponsesTable D-l. Power-On Self Test Error Message Test ResponsesTable D-2. Error Responses Error Code Message Explanation ERR? query ERR keyTable D-3. TEST? Responses Response Code Explanation TEST? queryManual Backdating Make ChangesGenerally Applicable Annotations II. CE’92 Product Specific Annotations6621A 6623AAgilent Sales and Support Office United States Latin AmericaManual Updates

6627A, 6621A, 6624A, 6623A, 6622A specifications

Agilent Technologies is renowned for its high-quality electronic test and measurement equipment, and the Agilent 6600 series is no exception. This series includes models like the Agilent 6621A, 6622A, 6623A, 6624A, and 6627A, each designed to meet the needs of various application requirements, making them an essential part of modern laboratories.

The Agilent 6621A is a single-output DC power supply that provides a stable output voltage and current, making it ideal for testing and powering electronic devices. It features a low noise specification, which is crucial for sensitive applications. With a maximum output voltage of 30V and a current of 3A, it offers flexibility for a range of projects, from powering prototypes to performing benchmark tests.

The Agilent 6622A, a dual-output model, enhances versatility by allowing users to power two devices concurrently. It delivers output voltages of up to 20V and a total output current of 5A, which is perfect for powering circuit boards with multiple components. The built-in voltage and current limiting functions protect the equipment under test, preventing any potential damage.

On the other hand, the Agilent 6623A provides additional capabilities with its three outputs, making it particularly suitable for complex testing procedures. With a maximum voltage of 20V and output current reaching 6A across all channels, it ensures that multiple loads can be powered simultaneously without compromising performance.

The Agilent 6624A further pushes these capabilities with its higher output power. This model boasts two outputs with a combined maximum output of up to 6A, supporting devices that require more demanding power levels. Its advanced control features allow for precise voltage and current adjustments, enhancing reliability during experiments.

Lastly, the Agilent 6627A stands out as a highly scalable power supply, capable of delivering up to 40V and 7.5A across its multiple outputs. This model is particularly beneficial for applications requiring higher voltages, enabling engineers and technicians to work with a broader array of components and systems.

All models in the Agilent 6600 series incorporate built-in protection features to guarantee safety during testing. They are equipped with memory functions, allowing users to save and recall settings quickly. Additionally, the intuitive interface and various connectivity options make these power supplies user-friendly, ensuring efficient workflow in any laboratory setting. In summary, the Agilent 6600 series offers a compelling combination of versatility, precision, and advanced features, catering to diverse electronic testing applications.