Agilent Technologies 6627A, 6621A, 6622A, 6623A, 6624A manual Wire Size Wire Bundled 10 a 20 a, Awg

Page 46

available in the load leads for prolonged operation into a 5 A load during ac low line at high ambient temperature conditions.

There is a similar stipulation for 80 W low voltage outputs at l0 A under the same conditions as above. See Figure 4-2A for worst case voltages available at the output terminals.

Table 4-1. Stranded Copper Wire Ampacity and Maximum Wire Lengths to Limit Load Lead Voltage Drop

 

Ampacity Per Wire (Amps)

Resistivity

Max Length to Limit

 

 

 

 

Voltage to 1 V Per Lead

Wire Size

2 Wire Bundled

4 Wire Bundled

 

5 A

 

10 A

20 A

(AWG)

 

 

(Ω/ft)

 

 

(feet)

 

20

7.8

6.9

0.0102

20

10

5

18

14.5

12.8

0.0064

30

15

7.5

16

18.2

16.1

0.0040

50

25

12.5

14

29.3

25.9

0.0025

--

40

20

12

37.6

33.2

0.0016

--

--

30

(Cross Section

 

 

(Ω/m)

 

(meters)

 

 

 

 

 

Area in mm2)

 

 

 

 

 

 

 

0.5

7.8

6.9

0.0401

5

2.4

1.2

0.75

9.4

8.3

0.0267

7.4

3.8

1.8

1

12.7

11.2

0.0200

10

5

2.6

1.5

15.0

13.3

0.0137

14.6

7.2

3.6

2.5

23.5

20.8

0.0082

--

12.2

6

Notes:

1.Ampacities for AWG wires are derived from MIL-W-5088B. Maximum ambient temp: 55°C. Maximum wire temp: 105°C.

2.Ampacities for metric wires are derived from IE Publication 335-1.

3.Ampacity of aluminum wire is approximately 84% of that listed for copper wire.

4.Because of wire inductance considerations, it is recommended that you keep your load leads twisted, tie wrapped, or bundled together and less than 50 feet (14.7 meters) in length per lead.

5.See pages 47 & 48 for information on wire gauge considerations with capacitive loads.

NOTE

To prevent tripping of the overvoltage circuit, pick a wire size sufficient to handle the FULL output

 

current of the unit no matter what the intended load current or current limit setting.

 

 

Table 4-1 lists the resistivity for various wire sizes and the maximum lengths to limit the voltage drop to 1.0 volts for various currents.

NOTE

The OVP circuit senses at the main output terminals and not on the sense leads. Thus, the voltage sensed

 

by the OVP circuit could be as much as 2 V higher than the voltage being regulated at the load. Program

 

the OVP trip voltage accordingly when using remote sensing. In addition, if the voltage drop exceeds 1.5

 

V on either load lead, a protective circuit will fire the OVP circuit regardless of the OVP setting.

Load lead resistance is an important factor relating to the CV stability of the supply with remote sensing of capacitive loads. If high capacitance loads are expected, you should not use wire gauges heavier than 12 to 14 AWG for long runs of load lead. See Figure 1-4 for more information about stability with output capacitors.

48 Output Connections and Operating Information

Image 46
Contents Operating Manual Agilent Part NoCertification Safety Summary Safety Summary Environmental ConditionsDeclaration of Conformity EMCWhat this Manual Contains Table Of Contents Remote Operation Local OperationCalibration Command SummaryError Messages Programming With a Series 200/300 ComputerIntroduction Safety ConsiderationsGeneral Information Instrument and Manual IdentificationModel AccessoriesDescription Output Combinations AvailableBasic Operation GP-IB BoardOutput Boards Qualifying Conditions SpecificationsDefinitions Output Response Characteristics Specifications Source EffectSupplemental Characteristics Outputs Low High Voltage Temperature CoefficientReadback Resolution OVPLow Voltage General Information General Information General Information General Information Initial Inspection InstallationLocation and Cooling Input Power Requirements Line FuseGP-IB Line FusesPower Cord Line Voltage ConversionGP-IB Interface Connector Getting Started Front Panel Controls and IndicatorsTurning On Your Supply 15V 35A Output Controls and Indicators Number Controls/lndicators Test Pattern of all Display Segments at Power-on Normal Self Test IndicationsChecking Out Your Supply Using Local Control Sample Self-Test Failure DisplayOvervoltage Test Voltage TestCurrent Test OCP Introduction To Remote OperationIset Enter RSTReading the GP-IB Address Sending a Remote CommandOutput AddrGetting Data From The Supply Often Used CommandsDisp a Disp a Returning the Supply to Local Mode Output Connections and Operating Information Output RangesOperating Quadrants Protection FeaturesRange Selection Typical Output Range Characteristics Connecting the Load Page Wire Size Wire Bundled 10 a 20 a AWGRemote Voltage Sensing Multiple LoadsRemote Voltage Sensing Remote Sense ConnectionsProgramming Response Time with an Output Capacitor Output Type FormulaOutput Noise Considerations Open Sense LeadsOvervoltage Trigger Connections External Trigger CircuitEquivalent Internal OV Trigger Circuit Battery Charging Power Supply Protection ConsiderationsParallel Operation Maximum Allowable Voltage Setting CV OperationCC Operation Remote SensingSeries Operation 13. Series Connections with Local Sensing CV OperationSpecifications for Series Operation 14. Series Connections with Remote SensingPage GP-IB Operation Remote OperationInterface Function GP-IB Address Selection Programming Syntax Power-On Service Request PONNumeric Data Sheet 1 of 2. Syntax Forms for Power Supply Commands Sheet 2 of 2. Syntax Forms for Power Supply Commands Power Supply Commands Header Output Channel Data RangePower Supply Commands Initial ConditionsVOUT? Voltage ProgrammingVSET? Current ProgrammingAvg Current-Avg RangeAvg Resolution IOUT?Range Switching Output On/OffOVSET? Overvoltage OV ProtectionOvercurrent Protection OCP Multiple Output Storage & Recall Clear CommandStatus Reporting Functional Relationship of Status Registers UNR +CCUNMASK? ASTS?Unmask 2,XXX Bit Assignment of the Serial Poll Register FAULT?Service Request Generation PON RQS ERR RDY FAUSRQ? Reprogramming Delay RQS BitDisplay On/Off Other QueriesTEST? CMODE?GP-IB Code Error Messages Explanation Front Panel ResponseTEST? Responses Front PanelResponse Code Code ExplanationLocal Control Of Output Functions Local ModeLocal Operation GeneralSetting Voltage Setting CurrentResetting Overcurrent Protection Setting Overvoltage ProtectionResetting Overvoltage Protection Displaying the Contents of the Fault RegisterLocal Control Of System Functions Setting the Reprogramming DelaySetting the Supply’s GP-IB Address ConditionSTO Enter Displaying Error MessagesAddr Enter RCL EnterCalibration Procedures Test Equipment and Setup RequiredFigure A-1. Calibration Setup Table A-1. Calibrat ion Commands Header Channel Data Syntax General Calibration ProcedureSee Figure Page Clear Voltmeter Output Buffer Calibration Program10 ! Calibration Example PauseDisp END of Calibration Program Input ANY More Outputs to CALIBRATE? Y or N,X$Fnend Page Path Names Programming With a Series 200/300 ComputerVoltage and Current Programming Voltage and Current Programming With Variables Voltage and Current ReadbackService Request and Serial Poll Programming Power Supply RegistersPrint OUTPUT1 is in CV Mode END if Present StatusPrint ’’OVERVOLTAGE on Output #1 Enable IntrOFF Intr Print Overvoltage on Output #2Error Detection Programming Outputs Connected In Parallel Stored Operating StatesInput Enter Voltage LIMIT’’,V Input Enter Operating VOLTAGE,V1Programming Outputs Connected In Series Input Enter the Desired Current Limit POINT,ITable C-1. Command Summary Command SummaryCommand Description Table C-l. Command Summary PON? ROM?SRQ? Table D-l. Power-On Self Test Error Message Error Codes and MessagesPower-On Self Test Messages Error Responses Test ResponsesTable D-2. Error Responses Error Code Message Explanation ERR? query ERR keyTable D-3. TEST? Responses Response Code Explanation TEST? queryManual Backdating Make Changes6621A Generally Applicable AnnotationsII. CE’92 Product Specific Annotations 6623AAgilent Sales and Support Office United States Latin AmericaManual Updates

6627A, 6621A, 6624A, 6623A, 6622A specifications

Agilent Technologies is renowned for its high-quality electronic test and measurement equipment, and the Agilent 6600 series is no exception. This series includes models like the Agilent 6621A, 6622A, 6623A, 6624A, and 6627A, each designed to meet the needs of various application requirements, making them an essential part of modern laboratories.

The Agilent 6621A is a single-output DC power supply that provides a stable output voltage and current, making it ideal for testing and powering electronic devices. It features a low noise specification, which is crucial for sensitive applications. With a maximum output voltage of 30V and a current of 3A, it offers flexibility for a range of projects, from powering prototypes to performing benchmark tests.

The Agilent 6622A, a dual-output model, enhances versatility by allowing users to power two devices concurrently. It delivers output voltages of up to 20V and a total output current of 5A, which is perfect for powering circuit boards with multiple components. The built-in voltage and current limiting functions protect the equipment under test, preventing any potential damage.

On the other hand, the Agilent 6623A provides additional capabilities with its three outputs, making it particularly suitable for complex testing procedures. With a maximum voltage of 20V and output current reaching 6A across all channels, it ensures that multiple loads can be powered simultaneously without compromising performance.

The Agilent 6624A further pushes these capabilities with its higher output power. This model boasts two outputs with a combined maximum output of up to 6A, supporting devices that require more demanding power levels. Its advanced control features allow for precise voltage and current adjustments, enhancing reliability during experiments.

Lastly, the Agilent 6627A stands out as a highly scalable power supply, capable of delivering up to 40V and 7.5A across its multiple outputs. This model is particularly beneficial for applications requiring higher voltages, enabling engineers and technicians to work with a broader array of components and systems.

All models in the Agilent 6600 series incorporate built-in protection features to guarantee safety during testing. They are equipped with memory functions, allowing users to save and recall settings quickly. Additionally, the intuitive interface and various connectivity options make these power supplies user-friendly, ensuring efficient workflow in any laboratory setting. In summary, the Agilent 6600 series offers a compelling combination of versatility, precision, and advanced features, catering to diverse electronic testing applications.