Toshiba instruction manual Installing the DEV002Z

Page 10

E6581295

3. Installing the DEV002Z

Install the DeviceNet option to VF-AS1/PS1 as follows:

*When this option is used together with the IO card option, attach this option to the front panel side.

(1)Turn off input power of VF-AS1/PS1 and wait for at least 15 minutes and then check that the CHARGE lamp on VF-AS1/PS1 is no longer lit.

(2)Securing the option to the inverter

a)Insert a flat-blade screwdriver in each of the two holes at the upper part of the front panel, release the panel mounting tab by pushing the screwdriver down, and remove the front panel cover.

b)Install the option in the inverter by fitting the tabs on the lower side of the option into the slots at the lower part of the inverter front panel.

c)Make sure the option is securely attached to the inverter. Then, check whether the plastic bosses on the inverter case have fitted in the holes at the upper and lower parts of the option.

d)Insert the tabs at the lower part of the front cover into the slots at the lower part of the inverter to attach the front cover to the inverter.

e)Stuck the enclosed "LED name label" on the option LED display part of a front

cover.

a)

*When installing this option to below capacities, remove the Add-on type option case.

VFAS1: 200V 55, 75kW

400V 90 - 500kW

c)

VFPS1: 200V 55 - 90kW

 

400V 90 - 630kW

 

b)

d)

LED name label

e)

 

MNS

MNS

MNS

MNS

MNS

- 9 -

Image 10
Contents Tosvert VF-AS1/PS1 Safety precautions Page Page Introduction Contents DEV002Z OverviewVF-AS1/PS1 VF-AS1/PS1 DEV002ZCanh Exterior featuresDeviceNet connector CanlDeviceNet indicator LEDInstalling the DEV002Z Connecting to the network Installation methodNetwork Grounding Setting a MAC ID number and a network baud rate MAC IDCommunications-related parameters F851 Communication Loss Action Setting Network breaks F852 Preset speed operation selectionReady F830 Assembly Object SettingAlarm ST/RUN ST/ RUNE6581295⑥ Data composition of output instance OFFST=ON ST=OFF ST=ONDeviceNet Local/Remote Operation VF-AS1/PS1 RR/S4 CCA SW1 Source SinkSpecifications Warranty