Toshiba DEV002Z instruction manual Exterior features, DeviceNet connector, Canh, Canl

Page 8

E6581295

2. Exterior features

The external view of this option and the name of each part are shown below:

DeviceNet indicator (Refer to Section 2.2)

Panel mounting tabs

(Refer to Section 3)

Dip switch

(Refer to Section 4.3)

DeviceNet connector

(Refer to Section 2.1)

Danger

Prohibited

Do not change the switch setting when the power is on.

It could lead to electric shocks, or the option might breaks down or get damaged.

2.1. DeviceNet connector

Used to connect DeviceNet network cables. The terminal is a plug-type and the signal of each terminal is as follows.

Color

Symbol

Signal classification:

 

 

 

Red

V+

Network Power Supply (V+)

 

 

 

White

CAN_H

Communication signal (High)

 

 

 

Silver

SHIELD

Shield

 

 

 

Blue

CAN_L

Communication signal (Low)

 

 

 

Black

V-

Network Power Supply (V-)

Size of connectable wire: 0.3 to 1.5mm2 (AWG 22 to 16), Strip-off length: 7mm

Tightening torque: 0.5 to 0.6 N·m

Recommended screwdriver: Small flat-blade screwdriver (blade thickness: 0.6mm, blade width: 3.5mm or less)

- 7 -

Image 8
Contents Tosvert VF-AS1/PS1 Safety precautions Page Page Introduction Contents Overview VF-AS1/PS1DEV002Z VF-AS1/PS1 DEV002ZExterior features DeviceNet connectorCanh CanlDeviceNet indicator LEDInstalling the DEV002Z Connecting to the network Installation methodNetwork Grounding Setting a MAC ID number and a network baud rate MAC IDCommunications-related parameters F851 Communication Loss Action Setting Network breaks F852 Preset speed operation selectionF830 Assembly Object Setting AlarmReady ST/RUN ST/ RUNE6581295⑥ Data composition of output instance OFFST=ON ST=OFF ST=ONDeviceNet Local/Remote Operation VF-AS1/PS1 RR/S4 CCA SW1 Source SinkSpecifications Warranty