Toshiba DEV002Z instruction manual Connecting to the network, Installation method

Page 11

E6581295

4. Connecting to the network

4.1.Installation method

(1)Attach DeviceNet cable to DeviceNet connector. (Refer to Section 2.1). (Be careful not to short-circuit adjacent terminals on DeviceNet connector).

<Recommended cable>

Thin branch cables: DeviceNet-specific thin cable. <Tightening torque>

0.5 - 0.6 N·m

Recommended screwdriver: Small flat-blade screwdriver (blade thickness: 0.6mm,

blade length: 3.5mm or less)

(2)Please set the terminating resistance if needed. <Terminating resistance specification>

1/4 W - 121 ohm, 1% Metal Film

(3)Using the DIP switch on the DeviceNet option, set a MAC ID number and a baud rate. (Refer to Section 4.3).

(4)Once all the parameters are set, the power must be cycled to the VF-AS1/PS1 for these changes to take effect. (Refer to Section 5.)

- 10 -

Image 11
Contents Tosvert VF-AS1/PS1 Safety precautions Page Page Introduction Contents VF-AS1/PS1 DEV002Z OverviewVF-AS1/PS1 DEV002ZCanl Exterior featuresDeviceNet connector CanhLED DeviceNet indicatorInstalling the DEV002Z Installation method Connecting to the networkNetwork Grounding MAC ID Setting a MAC ID number and a network baud rateCommunications-related parameters F852 Preset speed operation selection F851 Communication Loss Action Setting Network breaksST/RUN ST/ RUN F830 Assembly Object SettingAlarm ReadyOFF E6581295⑥ Data composition of output instanceST=ON ST=ON ST=OFFVF-AS1/PS1 RR/S4 CCA SW1 Source Sink DeviceNet Local/Remote OperationWarranty Specifications