4.2. Network Grounding

Please note the following points regarding the grounding of a DeviceNet network.

-Do not connect the G/E terminal to a power ground or any other potential noise-producing ground connection (such as a drive’s “E” terminal). Connect to a close, clean ground to provide RF termination of the DeviceNet cable.

-Do not make connections to unstable grounds (paint-coated screw heads, grounds that are subjected to inductive noise, etc.)

To prevent ground loops, the DeviceNet network should be earth grounded in only one location. No significant current flow between V- and earth ground may occur via any device other than a power supply under normal operating conditions.

(From the ODVA DeviceNet specification)

Power Tap

+

-

Node

Node

Node

Node

Power Spply

Node

 

Isolation barrier

- 11 -

Image 12
Contents Tosvert VF-AS1/PS1 Safety precautions Page Page Introduction Contents Overview VF-AS1/PS1DEV002Z VF-AS1/PS1 DEV002ZExterior features DeviceNet connectorCanh CanlDeviceNet indicator LEDInstalling the DEV002Z Connecting to the network Installation methodNetwork Grounding Setting a MAC ID number and a network baud rate MAC IDCommunications-related parameters F851 Communication Loss Action Setting Network breaks F852 Preset speed operation selectionF830 Assembly Object Setting AlarmReady ST/RUN ST/ RUNE6581295⑥ Data composition of output instance OFFST=ON ST=OFF ST=ONDeviceNet Local/Remote Operation VF-AS1/PS1 RR/S4 CCA SW1 Source SinkSpecifications Warranty