ADTRAN 1202890E1 NetVanta 4305 DC, Instructions for Connecting DC Power Source to the NetVanta

Page 50

Unit Installation

NetVanta 4300/4400 Series

 

 

NetVanta 4305 (DC)

The DC-powered NetVanta 4305 connects to a centralized DC power source via the four-position power connector on the rear of the chassis (see Figure 3 on page 18). The nominal input of the NetVanta 4305 is +24 VDC or -48 VDC. Power and ground connections require copper conductors and a ring lug.

 

Instructions for Connecting DC Power Source to the NetVanta 4305

 

 

Step

Action

1With the power disconnected, connect the primary power source to input A of the power connector.

2Connect a ground wire (fitted with a loop terminal end) to the grounding point using the screw provided. Connect the other end of the ground wire to a protective earth ground.

3If using a backup power source, connect it to input B of the power connector.

Power to the NetVanta 4305 DC System must be from a reliably grounded 24 or 48 VDC.

Use only copper conductors when making power connections.

Install unit in accordance with the requirements of NEC NFPA 70.

The branch circuit overcurrent protection shall be a fuse or circuit breaker rated minimum 48 VDC, maximum 10 A.

A readily accessible disconnect device, that is suitably approved and rated, shall be incorporated in the field wiring.

Maximum recommended ambient operating temperature is 50°C.

The 10/100Base-T and Gigabit Ethernet interfaces MUST NOT be metallically connected to interfaces that connect to the outside plant or its wiring. These interfaces are designed for use as intra-building interfaces only. The addition of primary protectors is not sufficient protection in order to connect this interface metallically to OSP wiring.

To comply with GR-1089-CORE, Issue 3, this equipment MUST only be installed in a DC-C (common) bonding and grounding environment. It may not be utilized in a DC-I (isolated) bonding and grounding environment.

50

Copyright © 2013 ADTRAN, Inc.

61200890E2-34R

Image 50
Contents NetVanta 4300/4400 Series Software Licensing Agreement TrademarksTo the Holder of the Manual Conventions Safety Instructions Save These Important Safety InstructionsFCC-Required Information REN/SOC FIC UsocIsdn BRI DIM Service and Warranty Toll Fraud LiabilityService and Warranty NetVanta 4300/4400 Series Table of Contents Table of Contents NetVanta 4300/4400 Series Appendix A. Connector Pin DefinitionsList of Figures List of Figures NetVanta 4300/4400 Series List of Tables List of Tables NetVanta 4300/4400 Series Introduction NetVanta 4305 Features and Specifications NetVantaNetVanta 4305 Shipping Contents NET/DBU and Wide Module Option Slots NetVanta 4305 Front Panel DesignNetVanta 4305 Rear Panel Design 10/100Base-T Ethernet Interface and Activity LEDs NetVanta 4430 Features and SpecificationsPower Supply SFP Module Slots NetVanta 4430 Shipping Contents NetVanta 4430 Domestic Shipping Contents NetVanta 4305 International Shipping ContentsNetVanta 4430 Rear Panel Design CompactFlashColor Indication NetVanta 4300/4400 Series Front Panel LEDsNetVanta 4300/4400 Series LEDs Option Modules Option Module Shipping Contents NetVanta Adsl NIM, Annex a 1202869E1 NetVanta E1/FE1 + G.703 Drop NIM 1200878E1/L1NetVanta Serial NIM 1200866E1 NetVanta Adsl NIM, Annex B 1202889E1NetVanta Isdn S/T DIM 1200875L1 NetVanta Analog Modem DIM 1200864L1NetVanta Isdn BRI DIM 1200865L1 NetVanta VPN Accelerator Card 1202368L1Network Interface Modules NetVanta 56K/64K NIM P/N 1200861L1T1/FT1 Interface Operating Modes DiagnosticsNetVanta T1/FT1 NIM P/N 1202862L1 NetVanta T1/FT1 Nebs NIM P/N 1200862L2#NEBS Operating ModesDSX-1 Interface NetVanta T1/FT1 + DSX-1 NIM P/N 1202863L1Operating Modes Clock Source NetVanta Dual T1 NIM P/N 1200872L1/1202872L1 T1 Interface8xE1 Interfaces NetVanta Octal T1/E1 Wide Module P/N 1202843E18xT1 Interfaces T1/E1 Mode DIP Switch Clock Source Physical NetVanta E1/FE1 NIM P/N 1200868E1/L1WAN-E1 Interface NetVanta E1/FE1 + G.703 Drop NIM P/N 1200878E1/L1 InterfaceSerial Interface Operating Mode EnvironmentalNetVanta Serial NIM P/N 1200866E1 NetVanta Adsl NIM, Annex a P/N 1202869E1 DSL Interface ComplianceNetVanta Adsl NIM, Annex B P/N 1202889E1 Adsl Interface ComplianceShdsl Interface Operating ModeNetVanta Shdsl NIM, Annex a P/N 1200936E1 NetVanta Shdsl NIM, Annex B P/N 1200937E1 NetVanta Shdsl NIM, Annex BNetVanta USB Wwan NIM P/N 1702803F1 USB Interface EnvironmentalNetVanta Analog Modem DIM P/N 1200864L1 Dial Backup Interface ModulesFeatures NetVanta Isdn BRI DIM P/N 1200865L1 NetVanta Isdn S/T DIM P/N 1200875L1 Etsi TBRUnit Installation Rack Mounting NetVanta 4300/4400 Series Tools RequiredMounting Options Step Action Wall Mounting NetVanta 4300/4400 SeriesInstructions for Wall Mounting the NetVanta Supplying Power to the Unit NetVanta 4305 AC and NetVantaInstructions for Connecting DC Power Source to the NetVanta NetVanta 4305 DCInstalling Dial Backup and Network Interface Modules Installing DIMsNIM and DIM Installation Using a USB Cellular Modem with the NetVanta USB Wwan NIM Instructions for Installing the VPN Accelerator Card NetVanta VPN Accelerator Card InstallationInstalling a Sodimm for Expandable Memory Instructions for Installing a SodimmSodimm Installation Keyed Slots Installing a CompactFlash Card Instructions for Installing a CompactFlash CardUnit Installation NetVanta 4300/4400 Series Appendix A. Connector PIN Definitions Table A-1 /100Base-T Ethernet Port Pinouts Name DescriptionTable A-3. SFP Slot Pinouts Name Table A-4. Console Port DCE Pinouts Name DescriptionTable A-7. WAN-E1 Connector Pinouts Table A-5. WAN-DDS Connector Pinouts Name DescriptionTable A-6. WAN-T1 Connector Pinouts Pin Name DescriptionTable A-10. WAN-ADSL NIM Connector Pinouts Table A-8. DSX-1 Connector Pinouts Name DescriptionTable A-9. G.703 Connector Pinouts Table A-11. WAN-SHDSL Connector PinoutsEIA Pin Table A-12. USB Wwan Connector Pinouts Name DescriptionTable A-13. Serial to Cable Pinouts Dial Backup Interface Module Pinouts DBU Connector Table A-15. Isdn S/T DBU Connector Pinouts